top of page

How to Size Air Handling Units (AHU) for Large Buildings

Mar 10
19 min read

Updated: Oct 3


An air handling unit is not correctly sized simply because its catalogue airflow matches the required CFM or L/s value. A defensible air handling unit sizing process must satisfy supply airflow, outdoor-air ventilation, cooling and heating capacity, humidity control, fan pressure, filtration, acoustics, physical space and part-load operation at the same time.


This engineering guide explains the complete AHU sizing calculation in SI and I-P units. It covers airflow, ventilation, mixed-air conditions, cooling-coil duty, chilled-water flow, coil face area, fan static pressure and motor power, followed by a detailed commercial-building example.


Quick answer: Calculate supply airflow from the zone sensible load, verify ventilation and process-air requirements, determine the mixed-air condition, size the cooling coil from the total enthalpy change, establish the AHU cross-section from component face velocity and select the fan from the actual critical-path pressure loss. Finally, verify humidity, acoustics, energy use, controls, access and part-load performance.

Go straight to your next design step:



The duct system converts the AHU airflow requirement into a fan-pressure requirement. For a detailed explanation of duct sizing, fitting losses, critical-path analysis and fan ESP reporting, review the HVAC Duct Pressure Loss Design Suite.


AHU sizing workflow

IMAGE 1: AHU sizing workflow

Air Handling Unit Dimensions: Typical Sizes by Airflow

The AHU cross-section is set by coil face velocity. Most manufacturers design for about 2.5 m/s across the cooling coil, so the coil face area is A (m²) = V (m³/s) ÷ 2.5. Casing, insulation and frame allowances are then added to get the overall width and height. Indicative sizes:

  • 1 m³/s (≈2,100 cfm): coil face ≈ 0.4 m²; unit roughly 1.0 m wide × 0.8 m high

  • 2.5 m³/s (≈5,300 cfm): coil face ≈ 1.0 m²; roughly 1.5 × 1.1 m

  • 5 m³/s (≈10,600 cfm): coil face ≈ 2.0 m²; roughly 2.0 × 1.5 m

  • 10 m³/s (≈21,200 cfm): coil face ≈ 4.0 m²; roughly 2.6 × 2.2 m

  • 15 m³/s (≈31,800 cfm): coil face ≈ 6.0 m²; roughly 3.2 × 2.5 m

Length depends on the sections fitted. A basic filter–coil–fan unit is often 2.5–4 m long, while units with heat recovery, mixing boxes, attenuators and humidifiers commonly reach 6–10 m. Confirm with the selected manufacturer, and keep coil-withdrawal and filter-access space about equal to the unit width on the service side.


What Does “AHU Size” Actually Mean?

AHU size is a group of coordinated performance requirements, not one number. Two AHUs with the same nominal airflow can have very different cooling coils, fan efficiencies, filter areas, pressure capabilities, casing leakage levels, sound performance and physical dimensions.

AHU parameter

What it controls

Consequence if selected incorrectly

Supply airflow, L/s or CFM

Space sensible load and air distribution

Poor temperature control, drafts or insufficient circulation

Outdoor airflow

Indoor air quality and building pressurization

Code noncompliance, excess humidity or unnecessary energy use

Cooling-coil duty, kW or TR

Sensible and latent cooling

High room temperature or poor humidity control

Heating-coil duty, kW

Winter heating and supply-air control

Low space temperature or unstable discharge air

Fan pressure, Pa or in. w.g.

Ability to move air through the system

Low airflow, excessive noise or high energy consumption

Filter efficiency and resistance

Air cleanliness and fan duty

Poor IAQ or falling airflow as filters become dirty

Face area and casing dimensions

Velocity, carryover, pressure drop and footprint

Condensate carryover, high pressure loss or installation problems

Sound power

Acoustic performance

Plantroom breakout noise or occupied-space complaints

Controls and turndown

Part-load stability and efficiency

Hunting, excess reheat, poor ventilation or wasted fan energy


Information Required Before Sizing an AHU

Collect the following information before using a manufacturer’s AHU selection program:

  1. Outdoor design conditions: Summer and winter dry-bulb temperature, coincident wet-bulb temperature or humidity ratio, altitude and barometric pressure.

  2. Indoor design conditions: Room temperature, relative humidity, permitted temperature variation and pressure requirements.

  3. Zone loads: Coincident sensible and latent cooling loads for each zone and the complete system.

  4. Ventilation requirements: Occupancy, floor area, exhaust, make-up air, outdoor-air rates and air-distribution effectiveness.

  5. System arrangement: CAV, VAV, single-zone, multizone, DOAS, 100% outdoor air, heat recovery, return fan or relief fan.

  6. Airside route: Duct dimensions, fittings, VAV boxes, terminals, fire/smoke dampers, louvers, silencers and leakage class.

  7. Coil data: Entering and leaving air conditions, chilled-water temperatures and allowable air- and water-side pressure drops.

  8. Project constraints: Plantroom space, access clearance, delivery route, module size, maintenance side, electrical supply, redundancy and acoustic limits.


Do not begin final AHU selection with a rule such as “400 CFM per ton” or “six air changes per hour.” These are useful reasonableness checks, but they cannot replace load, ventilation and psychrometric calculations.


Step 1 — Calculate the Cooling and Heating Loads

The space cooling load contains sensible and latent components:


Qtotal = Qsensible + Qlatent


Sensible load changes the air temperature. It includes:

  • Envelope heat gain

  • Solar gain through glazing

  • Sensible heat from occupants

  • Lighting heat

  • Equipment and appliance heat

  • Sensible infiltration load


Latent load changes the moisture content. It includes:

  • Moisture released by occupants

  • Humid outdoor ventilation air

  • Infiltration

  • Cooking or washing processes

  • Open water surfaces

  • Industrial moisture sources


For a central AHU, distinguish between the following loads:

  • Space load: Heat and moisture generated inside the conditioned zones.

  • Ventilation load: The energy required to condition outdoor air.

  • System gains: Fan heat, duct heat gain, duct leakage and return-air heat gain.

  • Cooling-coil load: The total duty experienced by the AHU cooling coil.


These values are not interchangeable. Cooling-coil duty is often considerably higher than the room cooling load, particularly in hot-humid climates and systems with high outdoor-air percentages.


Step 2 — Calculate Supply Airflow from the Sensible Load

For comfort cooling, supply airflow is normally determined from the space sensible load and the difference between room and supply-air temperatures.


SI equation


V̇s = Qs ÷ [ρair × cp,air × (Troom − Tsupply)]

At approximately standard indoor conditions, ρ × cp is commonly taken as 1.20 kJ/(m³·K):


V̇s (m³/s) ≈ Qs (kW) ÷ [1.20 × ΔT (K)]


I-P equation


CFM ≈ Qs (Btu/h) ÷ [1.08 × ΔT (°F)]

Where:

  • V̇s = supply airflow

  • Qs = space sensible cooling load

  • ρair = air density at the design condition

  • cp,air = specific heat of air

  • ΔT = room temperature minus delivered supply-air temperature


The constants 1.20 and 1.08 are approximations. Correct for actual air density when altitude, temperature or project requirements make the difference material.


Airflow calculation example

Assume:

  • Zone sensible load = 72 kW

  • Room temperature = 24°C

  • Delivered supply-air temperature = 13°C


Therefore:

V̇s = 72 ÷ [1.20 × (24 − 13)]

V̇s = 5.45 m³/s


This is approximately:

  • 5,450 L/s

  • 19,600 m³/h

  • 11,560 CFM


Why total cooling load must not be used

The temperature-difference equation carries sensible heat only. Substituting the total load, including latent heat, artificially increases the airflow and may still fail to provide adequate dehumidification.


Use the sensible load to calculate airflow. Handle latent load through the supply-air humidity ratio and cooling-coil enthalpy calculation.


Air changes per hour check

Some spaces are governed by ventilation, process, cleanliness or exhaust requirements.


For an ACH-based criterion:

V̇ (m³/s) = Room volume (m³) × ACH ÷ 3,600


In I-P units:

CFM = Room volume (ft³) × ACH ÷ 60


Compare the load-derived airflow with:

  • Minimum ventilation airflow

  • Mandatory air-change requirements

  • Exhaust make-up air

  • Pressurization requirements

  • Heating-air distribution requirements

  • Process-air requirements

Use the governing airflow and then recalculate the supply-air state and cooling-coil duty.


Step 3 — Determine the Required Outdoor Air

For many non-residential occupancies using the ASHRAE 62.1 Ventilation Rate Procedure, the breathing-zone outdoor airflow begins with:


Vbz = Rp × Pz + Ra × Az

The zone outdoor airflow is then adjusted for air-distribution effectiveness:


Voz = Vbz ÷ Ez

Where:

  • Rp = outdoor airflow rate per person

  • Pz = zone population

  • Ra = outdoor airflow rate per unit floor area

  • Az = zone floor area

  • Ez = zone air-distribution effectiveness


For a multizone recirculating system, the AHU outdoor-air intake may not be the simple sum of all zone outdoor-air values. System ventilation efficiency, occupant diversity, zone primary-air fractions and the ventilation-critical zone may determine the final intake.


For VAV systems, verify outdoor-air compliance at both peak airflow and minimum-flow operation.

Always use:

  • The standard edition adopted by the project

  • Local building and mechanical codes

  • Health authority requirements

  • Fire and life-safety requirements

  • Client or employer requirements


Hospitals, laboratories, kitchens, cleanrooms and industrial processes may require additional or entirely different ventilation criteria.


Important: Outdoor air is generally a fraction of the total AHU supply airflow. It is not automatically added on top of an airflow that already represents total supply. However, outdoor air increases the cooling, heating and latent load at the AHU coil.

Step 4 — Calculate the Mixed-Air Condition

In a recirculating AHU, the cooling coil receives a mixture of outdoor air and return air.

Cooling-coil duty must therefore be based on the mixed-air condition, not the return-air condition alone.


For a dry-air mass balance:

hm = xoa × hoa + (1 − xoa) × hra


Wm = xoa × Woa + (1 − xoa) × Wra


Where:

  • xoa = outdoor-air dry-mass fraction

  • h = moist-air enthalpy

  • W = humidity ratio

  • m = mixed air

  • oa = outdoor air

  • ra = return air


Use a psychrometric chart or validated software to calculate:

  • Mixed-air dry-bulb temperature

  • Wet-bulb temperature

  • Relative humidity

  • Humidity ratio

  • Enthalpy

  • Dew-point temperature


A dry-bulb weighted average is insufficient for cooling-coil sizing when humidity and latent load are significant.


For a 100% outdoor-air AHU or DOAS, outdoor air is the coil-entering condition. If energy recovery is installed, use the air condition leaving the recovery device and include its pressure drop, leakage, frost-control and bypass effects.

Psychrometric mixing and cooling process

IMAGE 2: Psychrometric mixing and cooling process

Step 5 — Size the Cooling Coil and Check Dehumidification

Total cooling-coil duty

Qcoil (kW) = ṁda (kg/s) × [hentering − hleaving] (kJ/kg)

Approximate dry-air mass flow can be obtained from:

ṁda ≈ ρair × V̇

In I-P units:

Qcoil (Btu/h) ≈ 4.5 × CFM × Δh (Btu/lb)

The 4.5 factor is based on standard-air assumptions. Use actual dry-air mass flow and project psychrometric properties for accurate engineering calculations.

Moisture removal and condensate

ṁcondensate = ṁda × (Wentering − Wleaving)

This moisture balance is essential in humid climates. A cooling coil may satisfy its sensible capacity while failing to achieve the required leaving-air humidity ratio.

The required supply humidity ratio can also be checked from the space latent load:

Wroom − Wsupply ≈ Qlatent ÷ (ṁda × hfg)

Where hfg is the latent heat of water vapour at the relevant condition.

Chilled-water flow

V̇water (L/s) ≈ Qcoil (kW) ÷ [4.186 × ΔTwater (K)]


The final coil must be selected using manufacturer software with:

  • Actual entering and leaving air conditions

  • Chilled-water supply and return temperatures

  • Airflow and density

  • Glycol concentration, if applicable

  • Allowable air-side pressure drop

  • Allowable water-side pressure drop

  • Corrosion and fouling requirements

  • Actual casing geometry

Cooling-coil input

Why it matters

Entering air DB/WB or DB/RH

Establishes the sensible and latent entering condition

Leaving air DB/WB or humidity ratio

Confirms temperature and dehumidification performance

Airflow and density

Determines dry-air mass flow and face velocity

Chilled-water temperatures

Determines water flow and required heat-transfer surface

Coil rows, fins and circuiting

Affect capacity, pressure drop and cleanability

Fin, tube and coating materials

Affect corrosion resistance and service life

Maximum face velocity

Controls pressure drop and condensate carryover

Drain-pan requirements

Protect downstream sections and ductwork from water carryover

Do not select a cooling coil by the number of rows alone. Two six-row coils can have substantially different capacities, fin densities, circuiting arrangements and pressure drops.


Hot-humid and Middle East design note

In Gulf and coastal climates, outdoor-air latent load can dominate the difference between room load and AHU coil load.


Use a coincident outdoor dry-bulb/wet-bulb or dry-bulb/dew-point condition from the project weather source. Do not combine peak dry-bulb temperature with an unrelated peak relative humidity.


Also verify:

  • Outdoor-air intake leakage

  • Building pressurization

  • Condensate quantity

  • Negative-pressure drain-trap depth

  • Wet-coil pressure drop

  • Fin and casing corrosion protection

  • Fan heat

  • Supply-duct heat gain

  • Energy-recovery leakage

  • Part-load humidity control


Step 6 — Calculate Coil Face Area and AHU Cross-Section

The preliminary coil face area is:

Aface = V̇air ÷ vface

If:

  • Design airflow = 5.45 m³/s

  • Preliminary cooling-coil face velocity = 2.2 m/s

Then:

Aface = 5.45 ÷ 2.2 = 2.48 m²

A nominal clear face of approximately 1.8 m × 1.4 m provides 2.52 m² before allowing for frames, blank-off plates and the manufacturer’s actual free area.

For preliminary comfort-cooling studies, designers often begin around 1.8–2.5 m/s or 350–500 fpm across a wet cooling coil.

Use the lower part of the range where:

  • Latent performance is important

  • Condensate carryover is a concern

  • Low pressure drop is required

  • Noise criteria are strict

  • Coil airflow distribution may be uneven


This is a preliminary range, not a universal limit. Verify the selected coil, drain pan, eliminator, filters and heat-recovery device at their actual rated velocities.

The final AHU width and height may be governed by the component requiring the largest face area—not necessarily the cooling coil.

The AHU length must include:

  • Mixing and transition sections

  • Filter sections

  • Coil sections

  • Access doors

  • Coil withdrawal space

  • Fan service clearance

  • Sound attenuators

  • Humidifier absorption distance

  • Drain-pan and trap arrangements

  • Controls and electrical panels

  • Delivery and module-splitting requirements

AHU components and airflow path

IMAGE 3: AHU components and airflow path


Step 7 — Calculate Static Pressure and Select the Fan

The AHU fan must deliver design airflow at the calculated system resistance.

Trace the critical index run from the relevant inlet or return point, through the AHU and along the most resistant supply path to the terminal device.

Do not add the pressure losses of parallel branches.


Fan pressure equation

ΔPfan = ΔPexternal critical path + ΔPinternal AHU + ΔPsystem effect + justified allowance

External-system losses

Internal-AHU losses

Straight supply and return duct friction

Filters at scheduled final resistance

Elbows, tees, transitions and offsets

Cooling and heating coils

VAV or CAV terminal units

Heat-recovery device

Fire, smoke and balancing dampers

Internal dampers and transitions

Diffusers, grilles and louvers

Internal sound attenuator

Applicable intake or exhaust path

Internal airflow-measurement station

External system effect

Casing and plenum losses

Clarify the AHU manufacturer’s terminology.

Some AHU schedules request external static pressure, because the manufacturer’s software calculates internal component losses separately. Other schedules require the complete fan static or total-pressure duty.


Never enter internal component pressure losses twice.


Dirty-filter pressure

Fan selection must consider the filter’s specified final resistance, not only its clean pressure drop.

As the filter loads with dust:

  • System resistance rises

  • Airflow may fall

  • Fan speed may increase

  • Fan power may increase

  • Noise may change

  • Cooling capacity may reduce if airflow is not maintained


Fan electrical input power


Pinput (kW) = V̇ (m³/s) × ΔPfan (Pa) ÷ [ηtotal × 1,000]

Where ηtotal is the combined efficiency applicable to the calculation boundary.

For separate efficiencies:


Pelectrical = V̇ × ΔP ÷ (ηfan × ηdrive × ηmotor)

Do not multiply efficiencies again if the manufacturer’s published value already represents complete fan-system electrical efficiency.


Specific fan power

SFP = Pinput ÷ V̇

Compare the result with the energy code adopted by the project.


Select the fan using certified performance data and verify:

  • The duty point is in a stable and efficient region

  • Absorbed power does not overload the motor

  • Air-density corrections are applied

  • Inlet and outlet system effects are included

  • VFD turndown is acceptable

  • Motor cooling is maintained

  • Sound power meets the acoustic design

  • Fan-array redundancy is defined where required

  • Backflow through inactive fans is controlled

  • Maintenance access is available



The HVAC Duct Pressure Loss Design Suite helps organize duct sections, calculate straight-duct and fitting losses, correct for air density, identify the critical path and prepare a recommended fan ESP report.


Step 8 — Select Filters, Heat Recovery, Casing and Accessories

Filtration

Choose filter efficiency according to the applicable:

  • Indoor-air-quality requirement

  • Mechanical code

  • Healthcare standard

  • Cleanroom classification

  • Client specification

  • Equipment protection requirement

Obtain both clean and final pressure drops at the actual face velocity.

Provide:

  • Differential-pressure indication

  • Dirty-filter alarm

  • Adequate replacement access

  • Proper filter seals

  • Sufficient filter-bank area

  • Safe maintenance clearance

A MERV or ISO classification indicates filtration efficiency; it does not define pressure drop. Use the selected filter manufacturer’s actual resistance data.


Energy recovery

Heat or energy recovery can reduce outdoor-air coil load, particularly in systems with high outdoor-air fractions.

However, it also introduces:

  • Additional supply-side pressure drop

  • Additional exhaust-side pressure drop

  • Fan energy

  • Maintenance requirements

  • Cross-leakage risk

  • Frost-control requirements

  • Bypass-control requirements

  • Possible contamination transfer

Compare recovered energy against additional fan power, maintenance and leakage risks.


AHU casing

Specify casing performance for:

  • Strength and deflection

  • Air leakage

  • Thermal transmittance

  • Thermal bridging

  • Acoustic insulation

  • Condensation resistance

  • Corrosion resistance

  • Outdoor weather protection

Confirm base height and condensate-trap depth against the fan suction pressure.

Coordinate:

  • Service-door swing

  • Coil and filter withdrawal space

  • Internal lighting

  • Viewing ports

  • Safe access

  • Drain connection and fall

  • Module splits

  • Lifting points

  • Door and elevator dimensions

  • Roof access

  • Flexible connections

  • Vibration isolation

  • Controls panels and cable routes


Acoustics

Request octave-band sound-power data rather than relying only on a single dBA value.

Assess:

  • Fan inlet sound

  • Fan discharge sound

  • Casing-radiated sound

  • Duct breakout and break-in

  • VAV-box regenerated noise

  • Diffuser and grille noise

  • Sound-attenuator insertion loss

  • Sound-attenuator pressure drop

  • Low-frequency fan noise

  • Structure-borne vibration


Step 9 — Verify Controls and Part-Load Operation

An AHU selected only at peak duty may perform poorly during most of the year.

Typical control functions include:

  • Supply-air temperature reset

  • Duct static-pressure reset

  • Minimum outdoor-air control

  • Outdoor-airflow measurement

  • Demand-controlled ventilation where permitted

  • Cooling-coil leaving-air control

  • Heat-recovery bypass

  • Economizer sequence

  • Freeze protection

  • Dirty-filter alarm

  • Condensate high-level alarm

  • Fan proof and airflow monitoring

  • Fan-array staging

  • VFD speed control

At minimum airflow, recheck:

  • Outdoor-air fraction

  • System ventilation efficiency

  • Cooling-coil face velocity

  • Dehumidification performance

  • Diffuser throw

  • Fan stability

  • Motor cooling

  • Room pressurization


Worked AHU Sizing Example

The following warm-humid-climate example demonstrates the calculation sequence for a recirculating chilled-water AHU.

The example is illustrative. Final equipment must be selected with project weather data, applicable codes and certified manufacturer software.

Design inputs

Input

Value

Zone condition

24°C, 50% RH

Zone sensible load

67 kW

Zone latent load

23 kW

Zone total load

90 kW

Outdoor airflow

0.90 m³/s

Outdoor condition

35°C DB / 26°C WB

Final supply condition

12°C, W ≈ 0.0076 kg/kg dry air

Cooling-coil leaving condition

Approximately 10°C, near saturation

Chilled-water temperatures

6/12°C

Preliminary coil face velocity

2.2 m/s


The zone load excludes the outdoor-air load. Ventilation must therefore be included in the AHU cooling-coil calculation.


1. Calculate supply airflow

At the selected supply humidity ratio:

cp,m = 1.006 + 1.86W

cp,m ≈ 1.020 kJ/(kg dry air·K)

The required dry-air mass flow is:

ṁda = 67 ÷ [1.020 × (24 − 12)]

ṁda ≈ 5.47 kg dry air/s


At a supply-air specific volume of approximately 0.818 m³/kg dry air:

V̇ = 5.47 × 0.818

V̇ ≈ 4.48 m³/s

Equivalent airflow:

  • 4,480 L/s

  • 16,100 m³/h

  • Approximately 9,500 CFM


2. Check the latent load

At 24°C and 50% RH:

Wroom ≈ 0.0093 kg/kg dry air

Selected supply humidity ratio:

Wsupply ≈ 0.0076 kg/kg dry air

Therefore:

Qlatent ≈ 5.47 × 2,500 × (0.0093 − 0.0076)

Qlatent ≈ 23 kW

This confirms that the selected supply humidity ratio can meet the zone latent load.


3. Check the total zone capacity

Air state

Humidity ratio

Enthalpy

Return air, 24°C and 50% RH

0.0093 kg/kg

47.8 kJ/kg dry air

Outdoor air, 35°C DB / 26°C WB

0.0175 kg/kg

80.2 kJ/kg dry air

Final supply air, 12°C

0.0076 kg/kg

31.3 kJ/kg dry air

Coil leaving air, approximately 10°C

0.0076 kg/kg

29.3 kJ/kg dry air

The total zone capacity is:


Qzone = 5.47 × (47.8 − 31.3)

Qzone ≈ 90 kW

The selected supply condition therefore satisfies both the 67 kW sensible load and 23 kW latent load.


4. Calculate mixed-air conditions

At the outdoor-air condition, the specific volume is approximately 0.898 m³/kg dry air.

Outdoor dry-air mass flow:

ṁoa = 0.90 ÷ 0.898

ṁoa ≈ 1.00 kg dry air/s

Outdoor-air dry-mass fraction:

xoa = 1.00 ÷ 5.47

xoa ≈ 0.183 or 18.3%

Mixed-air enthalpy:

hm = 0.183 × 80.2 + 0.817 × 47.8

hm ≈ 53.7 kJ/kg dry air

Mixed-air humidity ratio:

Wm = 0.183 × 0.0175 + 0.817 × 0.0093

Wm ≈ 0.0108 kg/kg dry air

The corresponding mixed-air dry-bulb temperature is approximately 26°C.


5. Calculate cooling-coil duty

Qcoil = 5.47 × (53.7 − 29.3)

Qcoil ≈ 134 kW

This equals approximately:

  • 38 TR

  • 457,000 Btu/h

The 134 kW cooling-coil duty is considerably higher than the 90 kW zone load because it includes:

  • Zone sensible and latent load

  • Outdoor-air treatment

  • Heat added between the coil and delivered supply condition

This demonstrates why matching an AHU cooling coil only to the room TR is unsafe.


6. Calculate chilled-water flow

For a 6 K chilled-water temperature rise:

V̇water = 134 ÷ (4.186 × 6)

V̇water ≈ 5.3 L/s

Equivalent flow:

  • 19.1 m³/h

  • Approximately 84 US gpm


7. Calculate condensate

ṁcond = 5.47 × (0.0108 − 0.0076) × 3,600

ṁcond ≈ 63 kg/h

This is approximately:

  • 63 L/h

  • 16.6 US gal/h

The drain pan, connection and trap must be designed for the calculated condensate rate plus a suitable drainage allowance.


8. Calculate coil face area

At a preliminary face velocity of 2.2 m/s:

Aface = 4.48 ÷ 2.2

Aface ≈ 2.04 m²

A nominal 1.5 m × 1.5 m coil provides 2.25 m² gross face area. The manufacturer must verify the net active area after allowing for frames and blank-off sections.


9. Calculate fan pressure

Assume the following verified pressure budget:

Pressure item

Design loss

Governing inlet branch

120 Pa

Critical supply duct, fittings and terminals

550 Pa

Filters at scheduled final resistance

220 Pa

Wet cooling coil

180 Pa

Internal dampers, transitions and casing effects

80 Pa

Explicit system-effect and commissioning allowance

50 Pa

Required fan pressure

1,200 Pa


Outdoor- and return-air branches are parallel before the mixing box. Their pressure losses must not automatically be added together. Use the governing balanced inlet path.


10. Calculate fan power

Air power:

Pair = 4.48 × 1,200

Pair ≈ 5.38 kW

Assume:

  • Fan efficiency = 72%

  • Direct drive

  • Motor efficiency = 92%

Electrical input:

Pelectrical = 5.38 ÷ (0.72 × 0.92)

Pelectrical ≈ 8.1 kW


If the motor and fan losses enter the airstream:

ΔTfan ≈ 8.1 ÷ (5.47 × 1.02)

ΔTfan ≈ 1.45 K


This supports the assumed temperature rise from approximately 10°C coil leaving air toward the 12°C delivered supply condition after fan and duct heat.


An 11 kW motor may be appropriate as the next standard size, but it must be confirmed against:

  • Manufacturer’s fan curve

  • Absorbed power across the operating range

  • Worst-density operating condition

  • VFD range

  • Motor overload condition

  • Stable operating region


Preliminary AHU selection summary

Parameter

Preliminary result

AHU supply airflow

4.48 m³/s / approximately 9,500 CFM

Outdoor airflow

0.90 m³/s / approximately 1,900 CFM

Cooling-coil duty

134 kW / 38 TR

Chilled-water flow

5.3 L/s / 84 gpm

Approximate condensate

63 L/h / 16.6 US gal/h

Minimum preliminary coil face area

2.04 m² / 22.0 ft²

Required fan pressure

1,200 Pa / 4.82 in. w.g.

Estimated fan electrical input

8.1 kW / 10.9 hp


AHU fan pressure path and duty point

IMAGE 4: AHU fan pressure path and duty point


The complete cooling-load design workflow

This example connects the room load, delivered supply condition and cooling-coil duty. The Cooling Load Design Handbook takes that calculation further, from building information and psychrometrics to supply airflow, system loads and preliminary equipment selection.

The 157-page PDF includes 18 chapters and three complete worked projects: a bedroom, a commercial office and a multi-room villa.

The preview request form asks for your first name and email.

Educational design reference. Use the project's adopted codes, design conditions and certified manufacturer data for final selection.

Common AHU Sizing Mistakes

Mistake

Correct approach

Using total cooling load in the sensible-airflow equation

Use sensible load for airflow and enthalpy for total coil duty

Selecting by 400 CFM/TR alone

Use CFM/TR only as a reasonableness check

Adding outdoor airflow twice

Establish whether outdoor air is part of the total supply or a separate DOAS stream

Calculating coil duty from return air only

Use mixed-air or post-energy-recovery conditions

Using ACH alone for comfort cooling

Compare ACH with load-derived airflow and use the governing condition

Selecting the fan from a typical ESP

Calculate actual critical-path pressure losses

Using only clean-filter resistance

Verify airflow at scheduled final filter resistance

Adding 10–20% to every quantity

Apply one documented allowance only where justified

Ignoring air density

Correct airflow, ventilation and fan selection for actual conditions

Ignoring fan and duct heat

Include downstream heat gains in the coil leaving-air requirement

Ignoring minimum VAV airflow

Recheck ventilation, humidity and diffuser performance at turndown

Using gross casing area as coil area

Use the net active coil face area

Ignoring delivery and maintenance

Check module size, access, weight and service clearance


AHU Selection Schedule Checklist

Before approving a vendor selection, confirm that the AHU schedule or submittal identifies:

  • Supply, return, exhaust and outdoor airflow

  • Peak and minimum operating conditions

  • Entering and leaving air DB/WB or humidity ratio

  • Total, sensible and latent coil capacities

  • Chilled-water or refrigerant conditions

  • Water flow and pressure drop

  • Clean and final filter pressure drops

  • Filter efficiency and classification

  • External and internal pressure-loss boundaries

  • Fan type, speed and efficiency

  • Fan absorbed power

  • Motor and VFD rating

  • Inlet, outlet and casing sound power

  • Casing leakage and strength

  • Thermal and acoustic casing performance

  • Heat-recovery efficiency and pressure drop

  • Heat-recovery leakage and bypass arrangement

  • Controls, sensors and alarms

  • Communication protocol

  • Overall dimensions and weight

  • Module splits

  • Service clearance and maintenance side

  • Drain-pan construction and trap requirements

  • Corrosion protection

  • Applicable certifications and standards


Frequently Asked Questions

How is AHU airflow calculated?

For comfort cooling, calculate airflow from the space sensible load and the difference between room and supply-air temperatures:

V̇ = Qs ÷ (ρ × cp × ΔT)

Then compare the result with ventilation, ACH, exhaust make-up, pressurization and process-air requirements.


How many CFM are required per ton of cooling?

Approximately 400 CFM/TR is a familiar comfort-cooling rule of thumb. However, the actual value changes with sensible heat ratio, supply-air temperature, climate and system type.

Calculate airflow from the sensible load and calculate coil tonnage from the total mixed-air enthalpy change.


What supply-air temperature should be used?

Approximately 12–14°C or 54–57°F is common for many comfort-cooling systems, but it is not universal.

Humidity control, diffuser performance, fan heat, duct gains, system type and zone sensible heat ratio may require a different temperature.


Can an AHU be sized using air changes per hour?

ACH is appropriate when ventilation, process or code criteria govern, such as in some hospitals, laboratories, cleanrooms, kitchens and industrial spaces.

For normal comfort cooling, ACH alone does not prove that sensible and latent loads are satisfied.


How is cooling-coil capacity calculated?

Use the dry-air mass flow multiplied by the enthalpy difference across the coil:

Qcoil = ṁda × (hentering − hleaving)

Use mixed air or air leaving the energy-recovery device as the entering condition.


How much spare capacity should be added?

There is no universal safety factor.

Use realistic coincident loads and add only documented allowances for:

  • Calculation uncertainty

  • Leakage

  • Fouling

  • Future tenant loads

  • Planned expansion

  • Coordination changes

Avoid adding independent safety factors to the load, airflow, coil, pressure and motor.


What static pressure should be used?

There is no reliable universal AHU ESP.

Calculate the critical route through:

  • Ducts

  • Fittings

  • Terminals

  • Filters

  • Coils

  • Dampers

  • Louvers

  • Sound attenuators

  • Heat-recovery devices

State clearly whether the manufacturer requires external static pressure or total fan pressure.


What is the difference between AHU airflow and tonnage?

Airflow primarily carries the space sensible load and supports ventilation and air distribution.

Cooling-coil tonnage represents the total sensible and latent heat removed from the entering air. Two AHUs with the same airflow can therefore require very different cooling capacities.


Final AHU Sizing Workflow

A professional AHU selection follows this sequence:

  1. Calculate coincident zone sensible and latent loads.

  2. Select an initial delivered supply-air condition.

  3. Calculate supply airflow from the sensible load.

  4. Verify ventilation, ACH, exhaust make-up and pressurization.

  5. Calculate outdoor- and return-air mixing conditions.

  6. Determine cooling-coil duty, leaving humidity ratio and condensate.

  7. Calculate chilled-water flow.

  8. Size the cooling-coil face and AHU casing.

  9. Calculate external and internal pressure losses.

  10. Select the fan at the required airflow, pressure and density.

  11. Verify motor power, sound and stable operation.

  12. Check filters, heat recovery, casing and accessories.

  13. Verify controls and minimum-flow operation.

  14. Coordinate dimensions, access, utilities and maintenance requirements.

  15. Review certified manufacturer selection data.

Correct airflow is only the beginning. A successful AHU must deliver that airflow through the actual duct system while controlling temperature, humidity, ventilation, noise and energy use throughout its complete operating range.


Use the suite to organize duct sections, calculate straight-duct and fitting losses, identify the critical path, correct for air density and prepare a recommended fan ESP report.


Related HVAC Design Guides

Technical References



Author note: Nexora Design Lab publishes practical engineering guidance on HVAC design, MEP systems, air distribution, pressure-loss calculations and sustainable building technologies.

Engineering disclaimer: This article is an educational design guide. It does not replace project-specific load calculations, governing codes, authority requirements or certified manufacturer selection data.

Comments

Rated 0 out of 5 stars.
No ratings yet

Add a rating
bottom of page