top of page
All Posts


VAV Minimum Pressure and Low-Flow Signal: Two Separate Checks
A VAV terminal can have enough inlet pressure and still measure its minimum airflow poorly. Check the pressure budget and sensor signal separately before changing fan pressure.
5 days ago4 min read


Parallel Fan-Powered VAV: Separate Primary and Discharge Airflow
A heating-mode diffuser reading includes both primary and locally recirculated air. Use the right flow for the controller, coil, fan and downstream pressure calculation.
5 days ago4 min read


Chiller Evaporator Approach: Diagnose Fouling Without Misreading the Trend
Use matched operating conditions, verified temperatures and an apparent-UA calculation to investigate rising chiller evaporator approach before prescribing tube cleaning.
6 days ago4 min read


Expansion-Vessel Precharge: Find the Missing Acceptance Volume
Calculate how an undercharged hydronic expansion vessel loses usable acceptance between cold fill and maximum operating pressure, then verify the installation safely.
6 days ago4 min read


MEP Material Wastage: Reconcile Purchased, Installed and Remaining Quantities
Keep net installation quantities, purchasing allowances and actual material losses separate. Follow a worked pipe-order example from stock-length rounding to a traceable site balance.
6 days ago4 min read


Variable-Flow Chillers: Commission the Flow Ramp During Staging
Translate the selected chiller’s flow-change limit into a measured ramp, then test isolation valves, pump response and flow proof through a one-to-two-chiller transition.
6 days ago4 min read


Warehouse Roof Heat Gain: Check the Heat Balance Before Adding Exhaust Fans
Compare roof heat entering a warehouse with the sensible heat its ventilation can remove, using a worked example that keeps airflow, indoor temperature and comfort limits separate.
6 days ago4 min read


Adding HVAC Noise Sources: A Logarithmic Decibel Calculation
Combine HVAC sound contributions at the same receiver correctly, estimate the benefit of treating one source, and avoid double-counting background noise.
6 days ago4 min read


Domestic Hot-Water Recirculation: Match Heat Loss, Temperature Drop and Pump Flow
Size recirculation flow from a defined heat-loss boundary, then check the farthest supply connection, complete hydraulic circuit and measured operating conditions.
6 days ago4 min read


Pitot-Tube Duct Traverses: Convert Each Pressure Before Averaging
Averaging Pitot velocity pressures before taking the square root inflates the calculated airflow. Work through the bias and set up a traceable traverse calculation.
6 days ago4 min read


AHU Filter Bypass: Inspect the Seal Before Trusting the Filter Rating
A correctly selected filter can still allow unfiltered air around its edges. Inspect the complete filter-bank sealing path and understand what pressure-drop readings cannot prove.
6 days ago4 min read


Belt-Driven AHU Fans: Separate Motor Speed, Pulley Ratio and Belt Slip
A low fan RPM does not automatically prove belt slip. Compare measured shaft speeds with the correct pulley pitch diameters, then check the load before making adjustments.
6 days ago4 min read
bottom of page