top of page

How to Size a Chilled Water Fan Coil Unit (FCU)

Chilled Water FCU Airflow Guide
Chilled Water FCU Airflow Guide

Selecting a chilled water fan coil unit by tonnage alone can result in poor cooling, high noise, excess energy use or humidity problems.


The selected FCU must meet the room’s total cooling load, sensible cooling load, required airflow and chilled-water flow at the project’s actual operating conditions.


New to HVAC equipment selection?



Information Required for FCU Sizing

Before selecting the fan coil unit, collect:

  • Room total cooling load in kW

  • Room sensible cooling load in kW

  • Indoor dry-bulb and wet-bulb temperatures

  • Chilled-water supply and return temperatures

  • Required supply airflow

  • Required external static pressure

  • Fresh-air load, if handled by the FCU

  • Maximum acceptable sound level

  • Available ceiling or installation space


Step 1: Determine the Room Cooling Load

Calculate both:


Total Cooling Load = Sensible Load + Latent Load


The calculation should consider:

  • Heat transfer through walls, roof and glazing

  • Solar heat gain

  • Occupants

  • Lighting

  • Electrical equipment

  • Ventilation air

  • Infiltration


Do not select an FCU using floor area alone. The accuracy of the FCU selection depends directly on the accuracy of the cooling-load calculation.


Need a structured method for calculating HVAC cooling loads?



Step 2: Calculate the Required Airflow (How to Size a Chilled Water Fan Coil Unit (FCU))


Airflow is normally estimated using the room’s sensible cooling load:


Airflow (m³/s) = Sensible Load (kW) ÷ [1.2 × Air Temperature Difference (°C)]


Where:

  • 1.2 is the approximate volumetric heat capacity of air

  • Air temperature difference = Room temperature − Supply-air temperature


Airflow Example

Assume:

  • Sensible cooling load = 6.4 kW

  • Room temperature = 24°C

  • Supply-air temperature = 14°C


Therefore:


Airflow = 6.4 ÷ [1.2 × (24 − 14)]

Airflow = 0.533 m³/s


This is approximately:

  • 533 L/s

  • 1,130 CFM


The selected FCU should deliver approximately this airflow at the intended operating fan speed.


Step 3: Calculate the Chilled-Water Flow


Use the total cooling load to calculate the required chilled-water flow:


Water Flow (m³/h) = 0.86 × Total Cooling Load (kW) ÷ Water Temperature Difference (°C)


Water-Flow Example

Assume:

  • Total cooling load = 8.0 kW

  • Chilled-water supply temperature = 7°C

  • Chilled-water return temperature = 12°C

  • Water temperature difference = 5°C


Therefore:

Water Flow = 0.86 × 8.0 ÷ 5

Required Water Flow = 1.38 m³/h


Once the water flow is known, the pipe, control valve and pump must be sized for the complete chilled-water circuit. (How to Size a Chilled Water Fan Coil Unit (FCU))



The Pump Head Calculator helps organize pipe-friction, fitting, valve and equipment pressure losses when determining the required pump duty.


Step 4: Select the FCU from Manufacturer Data

Use the manufacturer’s selection software or performance tables. Confirm that the FCU provides the required performance at the project’s actual conditions.


Check:

  • Total cooling capacity is equal to or higher than the total load

  • Sensible cooling capacity is equal to or higher than the sensible load

  • Airflow matches the calculated requirement

  • Chilled-water flow matches the design flow

  • Entering chilled-water temperature matches the project

  • Entering-air dry-bulb and wet-bulb temperatures match the design

  • Capacity is available at the intended fan speed

  • External static pressure is sufficient


Do not rely only on the nominal capacity printed in the model name. Nominal ratings may be based on different air and water conditions.


Step 5: Check External Static Pressure

For a ducted fan coil unit, the fan must overcome the resistance of the external air-distribution system.


Consider:

  • Supply and return duct friction

  • Bends, transitions and branch fittings

  • Supply diffusers and return grilles

  • Volume-control and fire dampers

  • Flexible duct connections

  • External filters or accessories


Confirm what is already included in the manufacturer’s published FCU rating to avoid double-counting pressure losses.



Use it to calculate duct and fitting pressure losses, identify the critical air path and check the required fan static pressure.


Step 6: Complete the Final Checks

Before approving the FCU, verify:

  • Coil water pressure drop

  • Control-valve size and authority

  • Pipe connection size

  • Sound level at the selected fan speed

  • Condensate drain and trap arrangement

  • Electrical supply and motor power

  • Thermostat and control requirements

  • Filter access and maintenance clearance

  • Unit dimensions and ceiling-space availability

  • Fresh-air connection, where applicable


Selecting the duty at medium fan speed can provide quieter normal operation while keeping high speed available as a reserve.


Quick FCU Sizing Example

For a room with:

  • Total cooling load: 8.0 kW

  • Sensible cooling load: 6.4 kW

  • Room/supply-air temperatures: 24°C/14°C

  • Chilled-water temperatures: 7°C/12°C


The approximate requirements are:

  • Airflow: 533 L/s or 1,130 CFM

  • Chilled-water flow: 1.38 m³/h

  • Total FCU capacity: At least 8.0 kW

  • Sensible FCU capacity: At least 6.4 kW


These capacities must be confirmed using manufacturer data at the stated air temperature, water temperature, water flow, fan speed and external static pressure.


A small selection margin may be used when required by the project, but avoid excessive oversizing or adding multiple safety factors.


Common FCU Selection Mistakes

Avoid:

  • Selecting from room area alone

  • Checking total capacity but ignoring sensible capacity

  • Using nominal capacity without checking rating conditions

  • Selecting a unit that meets duty only at high fan speed

  • Ignoring duct and filter pressure losses

  • Ignoring coil and control-valve pressure drops

  • Omitting or double-counting the fresh-air load

  • Adding excessive safety margins

  • Ignoring sound level and maintenance clearance


Complete Your FCU Design Workflow


A reliable FCU selection requires coordinated cooling-load, airflow, duct-pressure and chilled-water calculations.

Develop the room and zone cooling loads before selecting equipment.


Build a practical foundation in HVAC systems, calculations and equipment.


Calculate the required pump head for the chilled-water circuit.


Calculate airside pressure losses and verify the FCU’s required static pressure.


Final Selection Rule


Correct FCU selection = Correct cooling load + Correct airflow + Correct water flow + Sufficient static pressure + Manufacturer verification


Complete each step carefully, then select the fan coil unit that meets the calculated duty under the project’s actual operating conditions.

Comments

Rated 0 out of 5 stars.
No ratings yet

Add a rating
bottom of page