HVAC Fans in Series: Add Pressure at Equal Flow, Then Recalculate the Duty

Original illustrative engineering schematic. The worked calculation below uses explicit example inputs.
Putting a second fan in the same duct path does not mean adding its catalog airflow to the first fan’s airflow. In a series arrangement, essentially the same mass flow passes through both machines. At low pressure rise and approximately constant air density, the same volume flow can be used for both fan curves. Add the pressure rises at that common flow, then find where the combined curve meets the system requirement.
This is different from two fans feeding parallel branches into a common plenum. It is also different from two independently controlled fans serving separate pressure zones with significant leakage or intermediate branches. Draw the air path before choosing the arithmetic. A mistaken network diagram cannot be repaired by a more precise spreadsheet.
What the ideal combined curve means
ASHRAE’s 2024 fan chapter explains the theoretical pressure addition for series fans and cautions that transitions and nonuniform flow can reduce actual performance. AMETEK Rotron similarly distinguishes series and parallel arrangements. These principles support a preliminary calculation, not permission to install a second fan without manufacturer review.
Use a consistent pressure definition. Here both hypothetical fan curves are total-pressure-rise curves and the system curve represents total-pressure loss between matching boundaries. Do not add a fan-static-pressure curve to a total-pressure curve. Keep the inlet density and fan speed basis visible, and check whether the second fan’s inlet state differs enough to require correction.
Original example: one fan first
Suppose a fan has the illustrative curve Δp_f = 900 − 40 Q², where pressure is in Pa and Q is in m³/s. The unchanged duct system requires Δp_s = 60 Q². Assume steady incompressible flow, no intermediate branch or leakage, no control imposed flow limit and operation on a stable permissible portion of the curves. The coefficients are invented, not a rating for a named fan.
One fan: 900 − 40 Q² = 60 Q².
Q² = 9, so Q = 3.000 m³/s.
System pressure at this duty = 60 × 9 = 540 Pa.
This 3.000 m³/s is an installed operating point, not a catalog maximum. Compare ratings only on the same pressure definition and system boundary. The hypothetical total-pressure curves here are used only over the stated working range; they do not define a free-air-delivery rating.

Original hypothetical total-pressure curves. Added connection losses reduce the two-fan flow to 3.354 m³/s.
Add a second identical fan in series
For the idealized two-fan combination, pressure at every common flow is twice one fan’s pressure: Δp_pair = 1800 − 80 Q². The existing duct resistance remains 60 Q² in this first comparison. Solve the new intersection rather than multiplying the old duty flow by two.
1800 − 80 Q² = 60 Q².
Q² = 1800 / 140 = 12.857143.
Q = 3.585686 m³/s; system pressure = 771.429 Pa.
Each fan supplies 385.714 Pa at that common flow.
Airflow increases by approximately 19.5%, not 100%. At the original 3.000 m³/s, the pair could theoretically provide 1080 Pa while the duct needs only 540 Pa. That mismatch is why the operating point moves to higher flow. The system resistance then rises, while each fan’s available pressure falls, until the balance is restored.
Include the new interconnecting loss
A real series installation may add a transition or other connecting section. To illustrate the accounting, suppose its additional total-pressure loss is 20 Q² Pa. Assume, only for this second model, that the fan curves themselves remain valid after the connection. The new complete system curve becomes 80 Q².
1800 − 80 Q² = 80 Q².
Q² = 11.25; Q = 3.354102 m³/s.
Existing duct loss = 675 Pa; added connection loss = 225 Pa.
Combined fan pressure = 900 Pa, equal to the total 900 Pa loss.
The resulting increase over the original single-fan flow is 11.8%. This additional-loss model is not a universal system-effect correction. Inlet swirl, inadequate spacing and distorted velocity profiles can also change the fan’s effective performance. Do not represent those effects as a guessed coefficient and claim the result is a validated selection.
Power and failure cases still need separate checks
At the ideal pair duty, useful air power is Q × Δp /1000 =2.766 kW. With the stipulated added connecting loss it is 3.019 kW, despite the lower airflow. These are air-power values, not motor input power. Fan efficiency, drive and motor losses must be evaluated at each actual operating point before calculating electrical demand. No energy saving follows simply from adding a fan.
Obtain compatible curves for the exact fan size, speed, density and pressure convention.
Check both motors across the permitted operating range, not only at the intended duty.
Review stability and controls together so interacting controllers do not fight each other.
Assess the stopped-fan case with appropriate manufacturer data; a stationary fan is not a zero-loss open duct.
Confirm mechanical arrangement, access, vibration and sound requirements through the responsible designers.
The useful review output is one drawing of the flow path, one combined curve and a table of normal and abnormal operating cases. The Ventilation and Exhaust Design Handbook is a related design reference for taking the pressure budget into a broader system review. This example is ordinary ventilation analysis; it does not establish suitability for smoke control or any life-safety application.
Continue the calculation review
Sources and calculation basis