AHU Heat-Recovery Bypass: Compare Avoided Cooling Power with Added Fan Power

Illustrative engineering scene. The worked calculation below uses explicit example inputs.
A sensible heat-recovery core can cool incoming outdoor air and still increase total operating energy during mild weather. The recovered cooling is measured in thermal kilowatts. The extra fan requirement is input power. Comparing those two numbers directly gives the recovery core an advantage it has not earned: one kilowatt of avoided cooling load does not normally avoid one kilowatt of plant input.
A more useful decision compares the same system delivering the same airflow and supply condition with recovery enabled and with the designed bypass path open. This is an operating comparison, not permission to omit required recovery equipment or override a project sequence. It also differs from choosing the highest rated effectiveness during procurement.
Define what changes between the two modes
Include both air paths. Added resistance on the outdoor-air side may increase supply-fan input, and added resistance on the exhaust side may increase exhaust-fan input. Use the incremental resistance relative to the actual bypass route, not simply the clean core pressure drop. Bypass dampers, transitions and parallel pressure paths can change the difference.
A technical feature published by ASHRAE and hosted by Trane explains why the fan-power effect of recovery depends on how the device is integrated into the system. In a mixed-air arrangement, another path can already determine the required fan pressure. Therefore, adding a nominal component loss to total AHU fan pressure can exaggerate the real penalty.
The example below deliberately uses a dedicated outdoor-air arrangement whose incremental fan effects have been established. Both fans maintain their stated flows. Assume a sensible-only exchanger, no moisture transfer, dry operation, no leakage, and no frost mode. The cooling plant is operating in both modes and all recovered cooling is useful at the controlled supply condition.
Original example: calculate the additional input
Supply airflow: 3.00 m³/s; incremental pressure relative to bypass: 170 Pa; combined fan-drive efficiency: 0.65.
Exhaust airflow: 2.70 m³/s; incremental pressure relative to bypass: 140 Pa; combined fan-drive efficiency: 0.60.
Sensible effectiveness: 0.65 at these flows; minimum stream heat-capacity rate: 3.20 kW/K.
Marginal cooling-system COP: 4.20, meaning each avoided 4.20 kW of cooling avoids 1 kW of plant input at this operating condition.
Incremental supply-fan input = 3.00 × 170 / (1000 × 0.65) = 0.7846 kW. Incremental exhaust-fan input = 2.70 × 140 / (1000 × 0.60) = 0.6300 kW. Total incremental fan input = 1.4146 kW.
These combined efficiencies relate useful air power to input power. Do not divide by motor efficiency again if it is already included. In a field comparison, measured steady input-power differences are preferable to this simplified constant-efficiency estimate when the fans shift appreciably along their operating curves.
The thermal balance also needs the extra fan heat. Assume the supply-fan arrangement deposits its entire additional 0.7846 kW inside the cooled-air system boundary, with no supply-fan heat passing back through the recovery core, while the added exhaust-fan heat is discharged downstream of the exchanger and is not recovered. Thus 0.7846 kW must be removed by the cooling plant. Different motor and fan positions require a different heat allocation.

Recovery crosses the input-power break-even point at 3.234 K in the illustrative fixed-flow case, after incremental fan input and cooling-boundary fan heat are included.
Convert recovered cooling into avoided plant input
For sensible recovery, Qrec = ε × Cmin × ΔTin, where ΔTin is entering outdoor-air temperature minus entering exhaust-air temperature during cooling. Both temperatures are measured before recovery. Heat-capacity rate is mass flow multiplied by specific heat; do not infer equal capacity rates merely because two scheduled volumetric flows look similar.
At a 2 K entering-temperature difference: Qrec = 0.65 × 3.20 × 2 = 4.16 kW thermal. Avoided plant input = (4.16 − 0.7846) / 4.20 = 0.8037 kW. Net input-power saving = 0.8037 − 1.4146 = −0.6110 kW.
Recovery reduces the coil’s external cooling burden in this case, but its fan penalty is larger than the plant input avoided. The negative sign means full recovery uses about 0.61 kW more than the specified bypass mode. It does not mean the exchanger transfers heat in the wrong direction.
At an 8 K difference: Qrec = 16.64 kW thermal. Avoided plant input = (16.64 − 0.7846) / 4.20 = 3.7751 kW. Net saving = 3.7751 − 1.4146 = 2.3605 kW. The same hardware is now beneficial under the example assumptions.
Solve the operating crossover, then apply controls carefully
Set net saving to zero. ΔTcross = [COPmarginal × ΔPinput,fans + ΔQfan,to-cooled-air] / (ε × Cmin). Here ΔTcross = [4.20 × 1.4146 + 0.7846] / (0.65 × 3.20) = 3.234 K.
This threshold belongs to this operating point only. A more efficient cooling plant increases the amount of thermal recovery needed to justify a fixed fan penalty because each recovered thermal kilowatt avoids less input power. Lower airflow changes core effectiveness, pressure loss, fan efficiency and the two capacity rates. Recalculate rather than carrying one fixed threshold across every mode.
The formula assumes all the calculated recovery displaces active mechanical cooling. If the coil is already off, supply temperature is limiting, or recovery would introduce unwanted reheating, the useful recovery is smaller. Trane’s control guidance distinguishes these psychrometric modes and discusses bypassing an inactive recovery device to reduce fan energy.
Turn a screening result into a defensible operating test
Trend entering and leaving temperatures for both streams, airflow, bypass position, coil operation and fan input power on the same time basis.
Compare steady periods with the same delivered ventilation and supply-air requirement; avoid crediting reduced airflow as recovery efficiency.
Use manufacturer data or a validated field test for effectiveness and the pressure difference between the actual routes.
Include auxiliary power, such as a wheel drive or runaround pump, if the selected technology has it.
Confirm acceptable air quality, humidity, pressure relationships and the approved equipment sequence before changing operating logic.
The crossover should inform a control band, not a relay that changes mode at every tiny sensor fluctuation. Establish temperature uncertainty, minimum stable periods and an appropriate deadband during commissioning. A marginal 0.1 kW calculated advantage is not reliable if the combined measurement and plant-efficiency uncertainty is larger.
Finally, integrate the net benefit over actual operating hours before discussing annual energy. A strong design-day benefit does not establish seasonal savings, and a mildly unfavorable hour does not make the installed recovery device a poor investment. Capacity effects, installation cost and annual operating energy are separate decisions requiring separate evidence.
For a coordinated review of AHU heat recovery, fans, controls and commissioning evidence, get the complete AHU Selection & Fault Diagnosis Handbook. Use its checklists to document the system boundary before comparing supplier selections or interpreting site results.