Sensible Heat Recovery: Reconcile Unequal Air-Stream Heat-Capacity Rates

A heat-recovery selection lists 75% sensible effectiveness. The outdoor-air quantity is larger than the available exhaust quantity. Applying 75% directly to the outdoor-to-exhaust temperature difference can then overstate the supply-air temperature change. The missing step is identifying which air stream has the smaller heat-capacity rate. A consistent review calculates one heat-transfer rate and uses it to find both leaving temperatures.
Separate exchanger effectiveness from a supply temperature ratio
The 2024 ASHRAE Handbook chapter on air-to-air energy recovery defines transfer effectiveness relative to the maximum possible transfer. It also distinguishes metrics that can differ when supply and exhaust flows are unequal. Before using a supplier percentage, ask for its equation, operating conditions and measurement boundary. “Efficiency,” “effectiveness” and “temperature efficiency” are not sufficient definitions by themselves.
For a dry, sensible-only teaching model, define Cs = ms × cp,s and Ce = me × cp,e. The mass flows are in kg/s, specific heats in kJ/(kg·K), and capacity rates C in kW/K. Use a consistent mass basis: dry-air mass flow needs a specific-heat treatment expressed on that basis. Do not combine actual volume flow on one side with standard volume flow on the other without converting them consistently.
Let Cmin be the smaller capacity rate. For heating recovery, with exhaust entering warmer than outdoor air, Qmax = Cmin(Te,in − Ts,in). The actual sensible recovery is Q = ε × Qmax. The ASHRAE Fundamentals heat-transfer chapter develops this effectiveness approach and its dependence on exchanger configuration, thermal size and capacity-rate ratio. Here ε is a supplied performance input, not something calculated from airflow alone.
Work one unequal-flow case from both sides
Assume an original hypothetical selection with outdoor/supply inlet temperature Ts,in = 5°C, exhaust inlet temperature Te,in = 23°C, supply mass flow ms = 2.00 kg/s and exhaust mass flow me = 1.20 kg/s. Represent both streams with a rounded constant cp = 1.00 kJ/(kg·K). Assume ε = 0.75 is valid at these exact conditions. This simplified dry-air example excludes moisture transfer, condensation, frost, leakage, casing heat exchange and fan heat.
Supply capacity rate: Cs = 2.00 × 1.00 = 2.00 kW/K.
Exhaust capacity rate: Ce = 1.20 × 1.00 = 1.20 kW/K, so Cmin = 1.20 kW/K.
Available inlet temperature difference: 23 − 5 = 18 K.
Maximum sensible transfer: Qmax = 1.20 × 18 = 21.60 kW.
Actual sensible transfer: Q = 0.75 × 21.60 = 16.20 kW.
The supply air warms by Q/Cs = 16.20/2.00 = 8.10 K, leaving at 13.10°C. The exhaust air cools by Q/Ce = 16.20/1.20 = 13.50 K, leaving at 9.50°C. The heat gained and lost agree: 2.00 × (13.10 − 5.00) = 1.20 × (23.00 − 9.50) = 16.20 kW. Unequal temperature changes are exactly what the unequal capacity rates require.

Original dry, sensible-only example with cp = 1.00 kJ/(kg·K) on both sides and effectiveness 0.75 at the stated flows. Both heat balances give 16.20 kW; the supply temperature ratio is 45%.
The supply-side temperature ratio is (13.10 − 5)/(23 − 5) = 0.45, or 45%. The exhaust-side ratio is (23 − 9.50)/(23 − 5) = 0.75, or 75%. In this model, each ratio equals ε × Cmin/C for its respective stream. The smaller-capacity stream undergoes the larger temperature change.
Use the maximum-transfer check to expose an inconsistent selection
If the same example mistakenly uses Ts,out = 5 + 0.75(23 − 5), it predicts 18.50°C. The implied supply heat gain would be 2.00 × (18.50 − 5) = 27.00 kW. That exceeds this case’s 21.60 kW theoretical maximum and implies ε = 27.00/21.60 = 1.25. Under the stated dry, passive model, the inputs and output cannot all be correct.
This is a reason to reconcile the report, not immediately reject the physical unit. The percentage may be defined differently; the flows may use different bases; a fan or heater may be inside the temperature boundary; or the process may include condensation. Ask the supplier to identify the model and provide all four air states with matching flow data. Reconstructing the two balances is more useful than debating an unexplained percentage.
The downstream heating-coil consequence is tangible. For an illustrative 20°C supply target, the simplified coil load after correct recovery is 2.00 × (20 − 13.10) = 13.80 kW. Using the incorrect 18.50°C state would suggest only 3.00 kW. The difference is 10.80 kW in this teaching case. This is a boundary check, not a final coil selection or a promised energy saving.
Changing the airflow ratio requires a fresh performance point
As a separate numerical illustration, reverse the two mass flows while retaining the same inlet temperatures and an expressly assumed ε of 0.75. Cmin remains 1.20 kW/K and Q remains 16.20 kW, but supply now leaves at 18.50°C and exhaust at 14.90°C. The supply temperature ratio becomes 75% because supply is now the smaller-capacity stream.
That comparison explains the denominator; it does not predict the same exchanger after a flow adjustment. Changing flows changes heat-transfer coefficients, capacity-rate ratio and pressure drop. The effectiveness itself must be obtained for the new duty. The EnergyPlus 25.1 heat-exchanger engineering reference explicitly uses flow-dependent performance and separate heating/cooling inputs, illustrating why a single nominal percentage is incomplete.
Keep core performance and system operation distinct
A field check needs steady, representative measurements at the core boundaries. A temperature measured downstream of a supply fan includes a different energy balance from one measured immediately after the heat exchanger. Bypass position, leakage and any frost-control sequence also need to be known. Sensible recovery alone cannot establish the leaving humidity, net outdoor-air delivery or annual operating cost.
Label supply inlet/outlet and exhaust inlet/outlet on the same schematic.
Record both mass-flow bases, air states, bypass mode and the manufacturer’s effectiveness definition.
Calculate heat gain and heat loss independently, with measurement uncertainty stated. Investigate discrepancies rather than forcing a balancing factor.
Request the required full-load, part-load and control-mode selections; include the resulting pressure requirements in fan review.
Retain separate checks for moisture behavior, frost protection, leakage and applicable project requirements.
Carry the verified leaving state into the AHU review
The useful deliverable is a traceable heat balance with the reported recovery metric clearly defined. Carry its verified leaving-air state into downstream coil selection, rather than copying a headline efficiency into a temperature equation. For a structured way to review heat recovery alongside coils, fans and controls, use the paid Air Handling Unit (AHU) Selection & Fault Diagnosis Handbook. Its component and submittal-review coverage helps organize the evidence; project-specific manufacturer selections remain essential.