Air-Cooled Chiller Selection: Interpolate Capacity and Power Separately

Original illustrative engineering schematic. The worked calculation below uses explicit example inputs.
An air-cooled chiller comparison often starts with a nominal tonnage and an efficiency figure. Neither is enough to confirm a project duty. Capacity and electrical input must be evaluated at the specified entering condenser-air temperature, leaving chilled-water condition, fluid, flow and equipment configuration. When the design point lies between published points, interpolation may help, but only where the manufacturer permits it and the operating region is valid.
The useful habit is to interpolate cooling capacity and input power as separate quantities, then calculate COP from the results on a consistent boundary. Averaging two COP values is generally not the same calculation. The numerical differences can look small in one example and become larger when capacity and power vary more strongly or when a limit changes the operating mode.
Check permission and boundaries before arithmetic
Trane’s June 2015 CGAM catalog gives an example of manufacturer guidance that permits interpolation within its tabulated range and prohibits extrapolation beyond it. That historical document demonstrates the distinction; it is not evidence of present availability, a current project selection or permission to interpolate every chiller model. Obtain the applicable current selection data and manufacturer rules for the proposed equipment.
Read the power definition carefully. A table may distinguish compressor power from a rating boundary that includes condenser fans and controls. Do not divide capacity by one power value while labelling the result as an efficiency defined on another boundary. If notes conflict or the scope is unclear, resolve the ambiguity before using the result in a comparison. The original example below avoids that ambiguity by defining all power values explicitly.
Original two-temperature performance grid
Assume a fictional chiller has valid full-load data at entering condenser-air temperatures of 40 and 45°C and leaving chilled-water temperatures of 6 and 8°C. The fluid, evaporator temperature difference, altitude, fouling basis, frequency and equipment options are held fixed. Input power here includes compressors, condenser fans and controls, but excludes external pumps. The manufacturer is assumed to permit bilinear interpolation over this small rectangle with no intervening operating-mode limit.
At 6°C leaving water and 40°C entering air: capacity 300 kW; input 100 kW.
At 6°C leaving water and 45°C entering air: capacity 270 kW; input 112 kW.
At 8°C leaving water and 40°C entering air: capacity 324 kW; input 98 kW.
At 8°C leaving water and 45°C entering air: capacity 292 kW; input 110 kW.
These values are invented for teaching and must not be read as Trane ratings. The target is 43°C entering air and 7°C leaving water. Both coordinates lie inside the stated grid. The interpolation fractions are therefore 0.6 in the air-temperature direction and 0.5 in the leaving-water direction.
Interpolate along one axis, then the other
First find the 43°C entering-air values at each leaving-water row. Use y = y_low + f × (y_high − y_low), retaining capacity and power in different columns. At 6°C leaving water, capacity becomes 282.0 kW and input 107.2 kW. At 8°C leaving water, capacity becomes 304.8 kW and input 105.2 kW.
Capacity at 6°C LWT = 300 + 0.6(270 − 300) = 282.0 kW.
Capacity at 8°C LWT = 324 + 0.6(292 − 324) = 304.8 kW.
At 7°C LWT: capacity = 282.0 + 0.5(304.8 − 282.0) = 293.4 kW.
Input power = 107.2 + 0.5(105.2 − 107.2) = 106.2 kW.
COP on the stated unit boundary = 293.4 /106.2 = 2.7627.
The same answer follows by interpolating the water-temperature axis first. That is a useful spreadsheet cross-check for this bilinear model. It does not prove the physical model is appropriate across a compressor stage transition, control limit or excluded operating region. Interpolation cannot create valid data where the manufacturer has left a blank cell.

Original invented grid, not manufacturer ratings. All points share one stated unit-power boundary and an assumed valid interpolation region.
Compare the alternative COP calculation
At the four corners, COP values are 3.0000,2.4107,3.3061 and 2.6545. Bilinearly averaging those ratios gives approximately 2.7808 rather than 2.7627. The difference is about 0.65% relative to the ratio calculated after interpolating capacity and power. Do not adopt that percentage as a universal allowance; it arises solely from this invented grid.
The reason is algebraic: division is not a linear operation. If the manufacturer supplies a different approved selection method, use that method. Otherwise preserve the underlying capacity and power quantities so a reviewer can see what was interpolated and where the efficiency number came from.
Turn the result into a selection decision
Suppose the coincident project duty is 290 kW at exactly the stated conditions. The example offers only 3.4 kW of calculated capacity margin, about 1.17% of the duty. That is an arithmetic comparison, not a declaration that the selection is adequate. Design uncertainty, fouling assumptions, fluid properties, flow limits, control behavior and the responsible engineer’s criteria still require review.
Keep the original selection pages and their revision with the calculation.
Record both interpolation fractions and confirm each lies between zero and one.
Check the operating envelope and any staging or current limits separately.
Use entering condenser-air temperature at the equipment, not an unrelated weather reading.
Compare all proposed units on the same capacity, power and auxiliary boundary.
Request a manufacturer-generated selection for the actual design point before final acceptance.
The Chilled Water System Design Handbook is a related reference for connecting equipment selection to the wider plant design. This calculation is a review aid, not an equipment warranty, an electrical design or a forecast of annual energy. It makes one narrow question reproducible: what capacity and input power have been assigned to this particular operating point, and on what evidence?
Continue the calculation review
Sources and calculation basis
Primary references checked on 24 October 2026. The worked examples and diagrams are original illustrative calculations, not manufacturer selections or project approvals. Apply the stated limitations and the requirements governing the actual project.