Airflow Transmitter Scaling: Apply the Square Root Once, Not Twice

Original illustrative engineering schematic. The worked calculation below uses explicit example inputs.
An airflow station can agree at its full-scale point and still be substantially wrong across the operating range. One reason is a duplicated square-root calculation: the transmitter converts differential pressure into flow, and the building-management system converts that already-linear flow signal again. The opposite error occurs when neither device performs the conversion. Both mistakes disappear at 100% of span, so a single endpoint check is a weak test.
This is a signal-documentation and arithmetic review for a conventional differential-pressure airflow measurement. It is not an instruction to change a live controller, defeat an interlock or perform electrical work. A qualified controls and TAB team should confirm the actual sensor, output configuration and approved sequence before making any correction.
Identify what the wire represents
Yokogawa explains that square-root extraction can occur in the transmitter or in a controller and emphasizes documenting its location. For a fixed measurement element and density, volume flow is proportional to the square root of differential pressure. The proportionality constant must come from the applicable sensing-element calibration. A signal described only as “airflow, 4–20 mA” is insufficient: it might represent pressure awaiting conversion, or flow after conversion.
Normalized signal x = (I − 4 mA) / 16 mA.
For a pressure-linear output: Q / Q_full = sqrt(x).
For a flow-linear output: Q / Q_full = x.
The square root must appear once in the complete pressure-to-flow chain.
These equations assume zero-based, positive pressure and flow ranges. They do not cover a bipolar transmitter, a nonzero lower range, a custom transfer function or a sensor that supplies a digital compensated result. Read the documentation rather than forcing any of those devices into this simple model. The pressure range, airflow range and units all belong in the point schedule.

Illustrative 0–100 Pa and 0–2.00 m³/s ranges; fixed density and calibration.
Original half-flow example
Assume an illustrative station produces 100 Pa at 2.00 m³/s. Density and calibration are constant. At an actual flow of 1.00 m³/s, the pressure is 100 × (1/2)² = 25 Pa. If the transmitter sends a pressure-linear 4–20 mA output over 0–100 Pa, it sends 8.00 mA. The controller should normalize that to 0.25, take its square root and display 1.00 m³/s.
Pressure-linear path: 25 Pa → 8.00 mA → x = 0.25 → sqrt(x) = 0.50 → 1.00 m³/s.
Flow-linear path: 25 Pa → transmitter extracts root → 12.00 mA → x = 0.50 → 1.00 m³/s.
Wrong double-root path: sqrt(0.50) × 2.00 = 1.414 m³/s.
Wrong no-root pressure path: 0.25 × 2.00 = 0.500 m³/s.
The two correct paths use different current values at the same airflow. That is why comparing a current measurement with a generic flow percentage is not enough. In this example, the double-root error overstates half-flow by approximately 41.4%; omitting extraction understates it by 50%. Those are mathematical consequences of the invented signal chain, not typical field error rates.
Use intermediate points to expose the curve
Consider a true quarter-flow condition, 0.50 m³/s. Its differential pressure is 6.25 Pa. The pressure-linear current is 5.00 mA, whereas a correctly flow-linear transmitter sends 8.00 mA. Double extraction of the latter reports 1.00 m³/s, twice the actual example flow. At full flow, however, both wrong algorithms return 2.00 m³/s because the square root of one is one.
List the raw measurement unit and range, including the pressure reference.
Record the transmitter output mode separately from its local display mode.
Write the controller normalization and engineering-unit conversion explicitly.
Compare several stable intermediate points, not only zero and full scale.
Retain raw values, calculated flow and an independent reference measurement in the same record.
Do not confuse scaling with sensor accuracy
A corrected transfer function does not prove that the measurement is accurate. Zero drift, leaking or reversed pressure tubes, installation effects, density assumptions and an incorrect pickup constant can remain. At low pressure, small absolute errors can create large relative flow errors. Low-flow cutoff or signal damping may also change what is displayed near zero. Document those functions instead of interpreting a smooth zero as proof of no air movement.
Digital communications deserve the same review. A device may expose separate registers for raw differential pressure, calculated volume flow and standardized flow. A register label copied into a BMS database can be wrong even when its numerical units appear plausible. Confirm the selected register and its scaling against the device revision used on site. Do not mix actual and standardized airflow without an explicit density basis.
Close the discrepancy with a traceable record
The useful deliverable is a one-line signal map supported by configuration evidence: sensing element, pressure range, transmitter transfer function, output range, controller equation and final units. Add the test conditions and reference instrument, then record who approved any correction. Recheck the operating points after the authorized change rather than assuming the equation edit fixed the whole installation.
The Air Balancing Toolkit and field handbook are related resources for organizing airflow readings and reporting. This example does not claim that their workbook automatically diagnoses transmitter configuration. Keep the signal-chain review alongside the TAB report so a later technician can understand why the displayed airflow and the raw electrical signal have different percentages.