Booster Shutoff Pressure: Combine Maximum Inlet Pressure with Pump Shutoff Head

Oct 23
5 min read
Original conceptual engineering cover. Check the full pressure envelope. Add maximum inlet pressure, shutoff head and elevation.

Original illustrative engineering schematic. The worked calculation below uses explicit example inputs.


The normal duty calculation asks whether a booster can deliver enough pressure at the required flow. A pressure-rating review asks a different question: what pressure could each connected component experience when demand falls, inlet pressure rises, or an allowed operating mode reaches a higher pump speed? The two reviews need different boundary conditions. A satisfactory duty point cannot close the second question.


Consider a set selected to maintain an ordinary discharge setpoint. The control display may make that value look like a physical pressure ceiling. It is only an operating target unless the complete equipment and protection arrangement establishes otherwise. Before accepting the package, assemble the highest credible steady pressures using documented supply conditions and the actual selected pump curve.


Start with the pressure boundary, not a percentage allowance


Shutoff head is the head associated with zero delivered flow on the pump curve. It is a head increase across the pump, not the complete discharge gauge pressure. KSB identifies this zero-flow condition explicitly. At equal suction and discharge elevations, with zero external flow, discharge pressure is the inlet pressure plus the pressure equivalent of that head.



p_discharge = p_inlet + ρ × g × H0 / 100,000


Here p is gauge pressure in bar, ρ is kg/m³, g is m/s² and H0 is metres of pumped liquid.


For a connected stationary water column at elevation z:


p(z) = p_inlet + ρ × g × [H0 + z_pump − z] / 100,000.


Use one gauge-pressure reference throughout. The example places both pump connections at the same elevation and assumes the liquid remains hydraulically connected to the reviewed points. A closed isolation valve, pressure-reducing station, check-valve arrangement or separate supply can change the boundary. Mark those features on the schematic rather than silently carrying pressure through them.


Grundfos makes the additive inlet-pressure check explicit in its Hydro Multi-S product data: inlet pressure together with the closed-valve pump pressure must remain below the applicable maximum operating pressure. That manufacturer statement supports the method, but its published numerical product limits are not universal limits for another booster or its downstream fittings.



Illustrative static envelope with 4.8 bar gauge inlet pressure, 52 m pump shutoff head, water density 998 kg/m³ and g = 9.81 m/s²: discharge 9.891 bar, point 18 m above discharge 8.129 bar, and point 6 m below discharge 10.478 bar. No flowing friction allowance or transient surge is included.

Illustrative static envelope with 4.8 bar gauge inlet pressure, 52 m pump shutoff head, water density 998 kg/m³ and g = 9.81 m/s²: discharge 9.891 bar, point 18 m above discharge 8.129 bar, and point 6 m below discharge 10.478 bar. No flowing friction allowance or transient surge is included.


Worked example: the low point governs


  • Illustrative maximum steady inlet pressure at the pump: 4.80 bar gauge.

  • Selected maximum-speed curve: 52.0 m shutoff head, assumed to be its highest head for this example.

  • Water density: 998 kg/m³; gravitational acceleration: 9.81 m/s².

  • Pump connection datum: z = 0 m; low-point component: z = −6 m; upper component: z = +18 m.

  • Illustrative documented allowable steady pressure at the low-point component: 10.0 bar at the stated service conditions. This is not inferred merely from a nominal pressure-class label.


Pressure per metre = 998 × 9.81 / 100,000 = 0.0979038 bar/m.


Pump head contribution = 52 × 0.0979038 = 5.0910 bar.


At pump discharge: p = 4.80 + 5.0910 = 9.8910 bar.


At the low point: p = 9.8910 + 6 × 0.0979038 = 10.4784 bar.


At the upper point: p = 9.8910 − 18 × 0.0979038 = 8.1287 bar.


The low-point component exceeds the assumed 10.0 bar steady limit by 0.4784 bar even though the pump-discharge result is below 10.0 bar. A single pressure check at the booster would miss the governing location. The upper component has a lower pressure in this condition, but it still needs its own verified rating and other operating cases.


Do not subtract the design-flow pipe-friction schedule from this zero-flow result. The ordinary velocity-dependent losses disappear with external flow; the elevation contribution does not. This is one reason a large loss allowance in a duty calculation is not protective when reviewing closed-delivery pressure. A running minimum-flow bypass would create a different flow condition and must be represented explicitly.


Calculate the numerical boundary without calling it a safe setting


At the low point, the arithmetic ceiling on pump head is:


H0 = (10.0 − 4.80) / 0.0979038 − 6 = 47.1134 m.


This value leaves zero allowance within the assumed steady limit.


If maximum inlet pressure were actually 6.00 bar instead:


p_low = 6.00 + (52 + 6) × 0.0979038 = 11.6784 bar.


The 47.11 m result is useful for a selection discussion, not a recommended speed or protection setting. It uses exact assumed inputs and has no allowance for curve tolerance, pressure-measurement uncertainty, transient excursions or a different supply maximum. A responsible review must establish which allowances and protection requirements apply, then document the accepted configuration.


Likewise, the 6.00 bar sensitivity is a separate hypothetical supply condition, not a prediction of a particular utility. Obtain an appropriate maximum supply basis from the responsible provider and project records. A pressure reading during a busy daytime test may characterize an entirely different condition from the highest static pressure.


A lower normal speed does not remove the maximum-speed case


For an illustrative affinity-law sensitivity, keep the same impeller and assume shutoff head scales with speed squared. At 85 percent speed, the calculated shutoff head becomes 52 × 0.85² = 37.57 m. Under the same 4.80 bar inlet condition, the low-point pressure becomes 9.0657 bar. This shows why normal reduced-speed operation can look acceptable while another permitted mode does not.


Confirm the actual speed range and manufacturer curves rather than treating this scaling exercise as permission to change a setting. If a manual, fallback or commissioning mode permits full speed, the lower normal-speed calculation does not describe that mode. Conversely, do not invent a full-speed scenario if the documented hardware and approved control architecture physically exclude it. Record what is possible and how it is established.


Also inspect the whole selected curve. Some pump characteristics have a peak head at a nonzero flow that exceeds shutoff head; KSB distinguishes these two quantities. The original example assumes a curve whose maximum is at shutoff. If the actual curve differs, replace that assumption with the governing credible operating point and include the applicable local flow losses.



Build a component-by-component pressure schedule


  • Record the maximum supply pressure, its location and evidence, rather than reusing the minimum inlet pressure from the duty check.

  • Identify the selected pump, impeller, speed range and relevant curve tolerance. Do not borrow shutoff head from a neighboring model.

  • List component elevations and verified pressure-temperature limits for manifolds, vessels, valves, joints, instruments and connected equipment.

  • Separate normal control, permitted alternate operating modes and the independently reviewed protective functions.

  • Review transient pressure, trapped-liquid thermal expansion and commissioning/test pressures separately. A steady shutoff calculation does not bound those events.

  • Do not conduct a closed-valve running test solely to confirm this example. Follow manufacturer restrictions and an approved commissioning procedure.


Keep the normal service-pressure review alongside this maximum-pressure schedule. The existing booster-zoning guide explains elevation and residual pressure at fixtures; the head-unit guide explains the density conversion. Together they make the calculation boundary easier to audit without merging minimum-service and maximum-rating checks.




The Pump Head Calculator Design Suite provides an editable workbook for pipe and fitting losses, equipment drops, static head, pump duty, power and NPSH checks. Use it to organize the underlying duty calculation and report. Maintain the maximum-pressure schedule separately: the published product description does not establish automatic component-rating verification or transient simulation.



Continue the calculation review




Sources and calculation basis


Primary references checked on 23 October 2026. The worked examples and diagrams are original illustrative calculations, not manufacturer selections or project approvals. Apply the stated limitations and the requirements governing the actual project.