Chilled-Water Storage Discharge Tests: Integrate Only to the Temperature Cutoff

Original illustrative engineering schematic. The worked calculation below uses explicit example inputs.
A chilled-water tank may continue delivering cooling after its outlet has become too warm for the agreed duty. If a discharge-test spreadsheet integrates every kilowatt-hour until the pump stops, it can overstate the capacity available before that temperature limit. The missing step is to locate the cutoff in the time record and stop the useful-energy total at that point.
The earlier tank-sizing example used an assumed usable-capacity factor to convert ideal stored energy into a preliminary volume. This article addresses the next stage: reducing a discharge log into an observed useful-energy figure under specified test conditions. It is not a replacement for an agreed commissioning procedure or a supplier performance guarantee.
Define the test boundary before integrating
ASHRAE’s thermal-storage chapter defines the end of useful discharge by a predefined leaving-temperature limit. That distinction separates energy remaining in the storage medium from cooling that the connected duty can still use. For a direct-connected test, measure tank inlet return temperature, tank outlet supply temperature and the actual discharge flow on a consistent time basis.
State the initial charge condition, permitted outlet temperature, flow schedule, return-temperature schedule and any allowed interruption. Also identify whether instruments are on the tank side or across a heat exchanger. Heat-exchanger approach, pump heat and bypass mixing can otherwise move the measurement boundary without anyone changing the spreadsheet formula. The result should describe the boundary actually tested.
Cooling power P = rho × cp × Q × (T_return − T_outlet).
Use rho in kg/m³, cp in kJ/(kg·K), Q in m³/s and temperatures in °C: P is kW.
Useful energy = integral of P over time, ending at the agreed outlet-temperature cutoff.
With time in hours, the integrated result is thermal kWh.

Original illustrative log: 10 L/s,14°C return,linear interpolation; not a commissioning acceptance standard.
Original discharge-log example
Take an illustrative 150 m³ tank initially referenced to 6°C cold water and a 14°C warm-water condition. Assume constant discharge flow of 10.0 L/s, constant return temperature of 14.0°C, water density of 1000 kg/m³ and specific heat of 4.186 kJ/(kg·K). The agreed maximum outlet temperature for this teaching example is 8.0°C. It is a chosen duty limit, not a universal chilled-water standard.
Suppose outlet readings at 0, 1, 2, 3 and 4 hours are 6.0, 6.0, 6.5, 7.5 and 9.0°C. Assume linear change between the readings solely for this example. Real commissioning logs should normally have a much shorter interval around a moving thermocline and should document instrument uncertainty. These invented hourly values make the cutoff arithmetic visible.
Cutoff lies between hour 3 at 7.5°C and hour 4 at 9.0°C.
Fraction of that interval = (8.0 − 7.5) / (9.0 − 7.5) = 1/3.
Cutoff time = 3.333 hours.
At 10.0 L/s, rho × cp × Q = 41.86 kW/K.
Power at hours 0, 1, 2, 3 and cutoff = 334.88, 334.88, 313.95, 272.09 and 251.16 kW.
Integrate the truncated interval, not the whole row
For the stated constant-flow and constant-return assumptions, the linearly changing outlet temperature also gives linearly changing cooling power. The trapezoidal rule is therefore exact for this constructed log. Use the average of the two endpoint powers multiplied by each interval duration. The last duration is one third of an hour, not one full hour.
0–1 h: 334.88 kWh.
1–2 h: (334.88 + 313.95)/2 × 1 = 324.415 kWh.
2–3 h: (313.95 + 272.09)/2 × 1 = 293.020 kWh.
3–3.333 h: (272.09 + 251.16)/2 × 1/3 = 87.208 kWh.
Useful thermal energy to cutoff = 1039.523 kWh, approximately 1040 kWh.
Integrating the complete four-hour record instead gives 1193.010 kWh. The additional 153.487 kWh occurs after the example outlet limit has been crossed. It is not fictitious energy; it is energy delivered outside this particular temperature requirement. Keep it separately labelled if it is useful for another duty, rather than adding it to the claimed compliant test capacity.
Calculate a factor with an explicit reference
Ideal reference energy = 1000 × 4.186 × 150 × (14 − 6) / 3600 = 1395.333 kWh.
Observed useful-to-reference ratio = 1039.523 / 1395.333 = 0.745, or 74.5%.
This ratio describes this test and this reference temperature span. It is not a universal tank efficiency and should not be carried into a different flow, return temperature or cutoff without justification. A different initial charge, mixing history or sensor location can change the result. Gross structural volume must not be substituted for the stored-water volume used in the reference calculation.
Handle imperfect logs honestly
Retain original timestamps, units, quality flags and instrument identification.
Mark missing data rather than silently extending the previous reading through a long gap.
Locate the first agreed sustained cutoff crossing according to the approved test definition.
Calculate power at each synchronized observation before integrating; variable flow and temperature products require appropriate sampling.
Report useful energy, duration, peak discharge power and outlet-temperature history together.
A noisy reading close to the limit needs a pre-agreed decision rule, not selective deletion after the test. This example uses a simple first crossing in a monotonic, noise-free log. Actual acceptance criteria may specify persistence or another treatment, but that must be established by the responsible parties. State any interpolation and sensitivity to the sampling interval.
The next useful step is to add a cutoff timestamp and a truncated final interval to the existing discharge workbook, then have the result checked against the raw trend. The Chilled Water System Design Handbook provides related system-design context. This article does not claim that it includes an automatic thermal-storage acceptance calculator or that the illustrative result predicts any installation’s performance.
Continue the calculation review