Cooling ADPI: Check Draft and Air Speed Point by Point

AI-generated illustration of a mixed-air meeting room.
Measure where people sit
A diffuser can deliver its scheduled airflow and still leave a cold draft at one desk and warm, slow air at another. A hood checks what leaves the terminal. It does not show what happens to the air after it meets the ceiling, furniture and neighboring jets. Use an occupied-zone survey to investigate that difference.
Start with a plan marked with the intended occupied zone, outlet locations and agreed measurement points and heights. Record room loads, supply temperature, measured terminal flow and VAV mode. Test a repeatable cooling condition after temperatures and flow settle. The HVAC Duct Design and Sizing Handbook is a companion for outlet and duct selection. Verify actual product throw and installation separately.
Convert local conditions into a point screen
For a mixed-air cooling example, use the effective draft temperature equation in the ASHRAE Handbook chapter on room air distribution:
Effective draft temperature = (local air temperature − average room air temperature) − 8.0 × (local air speed − 0.15).
Use temperatures in °C and local speed in m/s. The coefficient 8.0 has units K per (m/s), and the result is in K. Count a point if the result is between −1.7 and +1.1 K and its measured air speed is below 0.36 m/s. These are the handbook’s cooling criteria for this example, not a project acceptance limit. The index is 100 × counted points ÷ valid survey points. Apply the speed check separately rather than averaging the readings before classifying points.
Use a low-speed instrument suited to the expected room air motion. Match the speed and temperature measurements at each location and height. Record the averaging period and instrument limitations. The Air Balancing (TAB) Toolkit is useful for separate terminal-flow records; the room point classification is calculated separately.
Work through eight fictional points
Assume the average room dry bulb is 24.0°C. At P6, 23.2°C and 0.31 m/s give (23.2 − 24.0) − 8.0 × (0.31 − 0.15) = −2.08 K. This falls below the temperature band. At P7, 24.4°C and 0.39 m/s give −1.52 K, inside the band, but the speed is too high for the point to count. At P5, 25.1°C and 0.13 m/s give +1.26 K, outside the warm end.
The other local temperature and speed pairs are P1: 23.9°C and 0.12 m/s; P2: 24.4°C and 0.17 m/s; P3: 23.9°C and 0.25 m/s; P4: 23.6°C and 0.30 m/s; and P8: 23.5°C and 0.20 m/s. All five meet both screens. For these inputs, the illustrative air diffusion performance index (ADPI) is 5 ÷ 8 × 100 = 62.5%. That is a fraction of sampled points, not a fraction of satisfied occupants. This sketch does not specify a compliant point count, grid, or measurement height. For formal room-air testing, follow the applicable project procedure and check ASHRAE Standard 113’s scope.

Fictional cooling survey: five of eight points meet both screens. This is not a field acceptance test.
Keep the locations, not just the score
Mark why each point missed the screen. A cold spot under a jet and a warm spot away from the jet call for different checks. Review outlet direction, obstructions, airflow and temperature at the agreed condition, then repeat at the same points after a change. If using a model to investigate the pattern, apply the CFD results review guide and compare predictions to suitable field evidence.
ADPI does not replace checks for vertical temperature gradients, radiant effects, humidity or outdoor-air delivery. For the separate catalog screening step, see diffuser throw at VAV minimum airflow.