High-Altitude AHU Cooling Coils: Rebuild the Dry-Air Mass and Moisture Balance

Oct 21
5 min read
Illustration of an air-handling unit on a mechanical terrace with a mountain landscape beyond.

Illustrative engineering scene. The worked calculation below uses explicit example inputs.


A sea-level AHU selection cannot be converted into a mountain-site selection by reducing its cooling capacity in proportion to atmospheric pressure. That shortcut changes the air mass but leaves the moisture properties untouched. If the entering condition is specified by temperature and relative humidity, humidity ratio also changes with pressure. The resulting sensible and moisture-removal duties do not follow one common correction factor.


The useful review question is therefore specific: what dry-air mass passes through the coil, and what thermodynamic change must each kilogram undergo at the project pressure? The example below rebuilds that calculation. It is a load-side check for a supplier enquiry, not a prediction that an unchanged physical coil will achieve the stated leaving condition.


Fix the pressure and the airflow location first


Use the site barometric pressure associated with the design basis. A standard-atmosphere estimate from elevation is a useful preliminary input, but it is not a measured weather condition. Also confirm that the pressure has not been corrected to sea level for a weather report. A station-pressure value and a sea-level-adjusted value describe different things.


Write the airflow as actual volume at a named state, such as the coil inlet. Without that location, 4 m³/s could mean warm entering air, cold leaving air or a standard-reference volume. These are not interchangeable. PsychroLib makes pressure an explicit input and labels moist-air specific volume per kilogram of dry air, which is the basis needed here.



ASHRAE defines humidity ratio as water-vapour mass divided by dry-air mass. Its psychrometric relationships distinguish that quantity from moisture fraction in the total moist-air mass. Keep the dry-air basis throughout the enthalpy and condensate calculations rather than multiplying dry-air-specific enthalpy by total moist-air mass.



Original example: identical temperatures and RH, different pressures


  • Actual entering airflow: 4.000 m³/s at the coil inlet.

  • Entering air: 30°C dry bulb and 50% relative humidity.

  • Required leaving air: 13°C dry bulb and 95% relative humidity.

  • Site pressure: 84.5 kPa absolute. Sea-level comparison: 101.325 kPa.

  • Steady operation, no casing leakage, no fan between the measurement planes, and negligible heat transfer through the casing.


These are illustrative comparison states, not climate recommendations. In particular, the 95% leaving relative humidity is an imposed target for this exercise, not a universal assumption for cooling-coil selections. The pressure comparison deliberately holds actual inlet volume, temperature and relative humidity constant to reveal what a pressure-only adjustment misses.


Use W = 0.621945 × pv / (p − pv), with pv = RH × pws(T). Use v = 0.287042 × (T + 273.15) × (1 + 1.607858W) / p, where p is kPa and v is m³/kg dry air. Then mda = Vactual / v. For this screening calculation, h = 1.006T + W(2501 + 1.86T), in kJ/kg dry air with T in °C.


At 84.5 kPa, the entering state gives W = 0.016029 kg/kg dry air, v = 1.056324 m³/kg dry air and h = 71.162 kJ/kg dry air. The leaving state gives W = 0.010652 and h = 39.977. These values were recomputed from the stated conditions, rather than copied from a sea-level chart.


Site dry-air mass flow = 4.000 / 1.056324 = 3.7867 kg/s. Approximate airside cooling duty = 3.7867 × (71.162 − 39.977) = 118.09 kW. Condensate production = 3.7867 × (0.016029 − 0.010652) × 3600 = 73.29 kg/h.


Repeating the complete property calculation at 101.325 kPa gives 4.5601 kg/s of dry air and an airside duty of 131.17 kW. The inlet humidity ratio is now 0.013310, and the outlet value is 0.008858. Both differ from their site-pressure counterparts even though the temperatures and relative humidities are identical.


Two separate bar charts compare dry-air mass flow of 4.5601 and 3.7867 kg/s and airside duties of 131.169 and 118.088 kW at 101.325 and 84.500 kPa.

At the same inlet volume, recomputing both psychrometric states gives different mass flow and airside duty. Illustrative imposed states, not equipment performance.


Why a single density multiplier gives the wrong answer


A pressure-ratio-only estimate would give 131.17 × 84.5 / 101.325 = approximately 109.39 kW. The rebuilt site calculation gives 118.09 kW, approximately 8.70 kW higher. For these imposed states, condensate is 73.29 kg/h at site pressure versus 73.08 kg/h at sea level.


The near-equal condensate figures are a result of this particular comparison, not a general altitude rule. Lower dry-air mass flow is largely offset by the larger humidity-ratio difference. Holding humidity ratio constant instead of relative humidity would define a different experiment and yield a different result. Always state what the comparison holds constant.


The cold leaving actual volume is also different from the entering volume. At the site leaving state, v is 0.988685 m³/kg dry air, so the outlet volume is 3.7439 m³/s. A schedule that repeats 4.000 m³/s at both ends without explaining its reference basis creates a discrepancy even when dry-air mass is conserved.


Separate an airside check from the manufacturer selection


The 118.09 kW result is the moist-air enthalpy decrease. For an exact coil energy balance, account for energy leaving in the liquid condensate. If condensate leaves at an assumed 13°C, its approximately 1.11 kW liquid enthalpy flow reduces the corresponding heat transferred to the coolant to about 116.98 kW. Actual condensate temperature and the chosen reference convention must be consistent.



Do not convert either number into a blanket derating of catalog capacity. A real coil has a particular surface, circuiting and heat-transfer response. Changing air density, volume, water conditions or face velocity changes its operating point. Request a selection at the project pressure and stated states, including achieved leaving humidity, sensible and total duty, and both pressure drops.


A review sequence that exposes the mismatch


  • Mark the pressure, altitude basis, airflow reference state and measurement plane on the enquiry.

  • Recompute every psychrometric state at the same site pressure before calculating mass flow or mixing.

  • Keep room sensible duty, required supply condition, mixed-air coil duty and fan heat on separate boundaries.

  • Ask the supplier to identify whether its airflow field accepts actual or standardized volume and how it applies altitude.

  • Reconcile the selected airside duty, moisture removal and coolant duty with the same assumptions before accepting the selection.


The conclusion should be a traceable schedule, not an isolated correction factor. Include the imposed leaving condition, the calculated dry-air mass, the moisture-removal requirement and the exact supplier rating conditions. That lets the next reviewer distinguish a load-basis error from a genuine equipment-capacity shortfall.


For a broader workflow covering AHU specifications, coil review, offer comparison and commissioning checks, get the complete AHU Selection & Fault Diagnosis Handbook. Its worked examples and checklists support engineering review; final capacity still requires manufacturer selection data.