Humidity Trend Averages: Convert Each Temperature–RH Pair Before Averaging Moisture

AI-generated illustrative scene, not a product screenshot or a completed-project photograph. The worked calculation below uses explicit example inputs.
A daily report lists an average temperature of 25°C and an average relative humidity of 60%. It is tempting to enter those two numbers into a psychrometric calculator and call the result the day's average moisture content. That shortcut can be wrong because the conversion depends nonlinearly on temperature and humidity together.
The right calculation depends on the question. Average RH can be a useful descriptive statistic for an RH record. Average humidity ratio answers a different question about water vapor per unit dry air. Moisture transported through an AHU requires an additional dry-air mass-flow weighting. Keep those outputs separate instead of treating one average as a universal air state.
Convert paired observations, not unrelated summaries
Vaisala explains RH as the ratio of water-vapor partial pressure to saturation pressure at the same temperature, and mixing ratio as water mass per dry-gas mass. The ASHRAE psychrometric relationships provide the corresponding engineering conversion. For this example, use water-vapor partial pressure pv = φ × pws(T), where φ is RH expressed as a fraction.
Humidity ratio is W = 0.621945 × pv/(P − pv), using consistent pressure units. Here P is total absolute air pressure, not a gauge reading. The saturation pressure pws changes with temperature, so averaging temperature first generally loses information needed for the conversion. Pair each RH value with the temperature and pressure basis that belongs to it.
Original two-state example
Assume two one-hour periods at a constant absolute pressure of 101.325 kPa. During the first, air is at 20°C and 80% RH. During the second, it is at 30°C and 40% RH. Use rounded saturation pressures of 2.339 kPa at 20°C, 4.246 kPa at 30°C and 3.170 kPa at 25°C for this illustrative calculation.
State A: pv = 0.80 × 2.339 = 1.8712 kPa; W = 11.702 g/kg dry air.
State B: pv = 0.40 × 4.246 = 1.6984 kPa; W = 10.603 g/kg dry air.
Equal-duration mean W = (11.702 + 10.603)/2 = 11.152 g/kg dry air.
Mean inputs: 25°C and 60% RH → pv = 1.902 kPa → W = 11.898 g/kg dry air.
Converting the averaged inputs overstates the time-average humidity ratio by approximately 0.746 g/kg dry air, or 6.7% relative to 11.152. This is a consequence of the invented two-state sequence, not a typical sensor bias or an expected saving from a control change. Other sequences can produce a different magnitude or direction of error.
Notice that the cooler, higher-RH period actually has more water vapor per kilogram of dry air than the warmer, lower-RH period in this example. An RH percentage alone is therefore insufficient to compare moisture content across changing temperatures. Keep the two original states visible so readers can reproduce the result rather than seeing only the daily summaries.

101.325 kPa; rounded illustrative saturation pressures; time average, not a mixing calculation.
Time weighting and transported moisture are different
If the first state lasts three hours and the second lasts one hour, the time-average W is (3 × 11.702 + 10.603)/4 = 11.427 g/kg dry air. Equal weighting would no longer represent the reporting duration. Use the actual sample intervals and document how readings represent the periods between timestamps.
For moisture carried by a varying air stream, weight W by dry-air mass transported, not just elapsed time. If equal-duration states A and B have dry-air mass flows of 1 and 2 kg/s, respectively, the transported-air average becomes (1 × 11.702 + 2 × 10.603)/3 = 10.969 g/kg dry air. This is not the same as an equal-duration average.
Neither result is automatically the final state of physically mixed air. A mixing calculation also requires an energy balance, compatible pressure assumptions and a saturation check. This article concerns data reduction, not coil sizing or prediction of condensate formation. Do not use a single daily average to replace peak humidity conditions required for design.
Preserve pairing and coverage
Temperature and RH timestamps must describe the same air sample closely enough for the intended analysis. Different sensor response times, time offsets and sampling intervals can create artificial pairs during rapid transitions. Investigate these issues rather than interpreting every computed spike as a real moisture event.
Retain invalid-data flags, instrument range limits and condensation-related sensor warnings. Missing RH is not zero RH. A gap in one channel means the derived property is unavailable unless a justified method supplies it; any estimation should be labeled separately. Report the fraction of the period with valid paired data alongside the average.
Deliver a useful humidity summary
A reproducible export contains timestamp, temperature, RH, pressure basis, calculated W, interval duration and quality flag. Add dry-air flow only when the engineering question requires moisture transport. Retain extremes and duration distributions separately from the average so that a short important excursion does not disappear inside a daily mean.
The next step is to choose the statistic that matches the decision before changing a control setpoint. The AHU Selection and Fault Diagnosis Handbook is a related engineering reference. This standalone example does not claim that the handbook imports trend logs or automatically diagnoses sensors, and it does not establish a health, comfort or regulatory acceptance limit.
Continue the calculation review