Proportional Air Balancing: Compare Percent of Design Before Adjusting Total Flow

Oct 15
4 min read
Original technical illustration of three air terminals with different design flows connected to one branch, emphasizing equal percent of design.

Three supply terminals deliver 180, 240 and 580 L/s. The smallest reading belongs to the smallest room, so it may be entirely appropriate. A useful balancing comparison divides each measured airflow by its own design airflow. Proportional balancing aims to establish the required distribution between terminals before the final total-flow adjustment. Confusing equal flow with equal percentage can leave a neatly documented system supplying the wrong rooms.


1. Establish a stable test condition


This example concerns a conventional constant-air-volume branch with manual balancing dampers. It is a calculation and review exercise, not a substitute for the project commissioning method. Confirm the system is ready, the terminals and filters are in their intended condition, and access is available. Identify controls that might change airflow while readings are taken, and use the approved test mode. Record and later remove temporary overrides through the agreed commissioning process.


CIBSE Journal’s January 2025 overview of Commissioning Code A: Air Distribution Systems, 2024 describes the initial scan, identification of the least-favoured terminal and avoidance of excessive restriction. It also distinguishes conventional CAV regulation from VAV systems, whose controls require a tailored procedure. These are UK-oriented professional references; the project specification determines the adopted procedure and acceptance limits.


Use the correct measuring method for each terminal, including any applicable hood correction or manufacturer factor. Keep measured and design flows on the same actual or standard-air basis. An accurate division cannot rescue an incorrect airflow measurement. A zero design flow also makes the usual percentage undefined; resolve the schedule or operating-mode issue instead of forcing a spreadsheet result.


2. Find the lowest percentage rather than the lowest airflow


Assume three terminals on one branch have design airflows A = 200 L/s, B = 300 L/s and C = 500 L/s. Their total is 1,000 L/s. The initial measured flows are A = 180 L/s, B = 240 L/s and C = 580 L/s. All numbers are original hypothetical readings, and no unmeasured outlets or leakage are included in this simplified branch balance.


  1. Terminal A: measured/design = 180/200 = 0.90, or 90% of design.

  2. Terminal B: 240/300 = 0.80, or 80% of design.

  3. Terminal C: 580/500 = 1.16, or 116% of design.

  4. Total: (180 + 240 + 580)/(200 + 300 + 500) = 1.00, or 100% of design.


The branch already has its design total, yet the distribution is unsuitable. B is the initial least-favoured terminal because it has the lowest measured-to-design ratio. A has the lowest absolute airflow, but its relative shortfall is smaller. A total-flow reading alone would miss this problem. The unweighted mean of the three percentages is 95.3%, which is also not the branch’s 100% total-flow ratio; design quantities provide the necessary weighting.


3. Recheck the reference as adjustments redistribute air


At the initial B ratio of 0.80, the corresponding proportional targets would be 160 L/s for A, 240 L/s for B and 400 L/s for C. These are temporary comparison values. They are not guaranteed final readings after throttling A and C, because changing branch resistances changes the network operating condition and can increase B’s flow.


Suppose a later stable scan finds B = 270 L/s. Its current ratio is now 270/300 = 0.90. The corresponding targets become A = 180 L/s and C = 450 L/s. If C is currently delivering 500 L/s, it is 100% of its own design while B is 90%. C’s ratio relative to B is 1.00/0.90 = 1.111. The appropriate comparison is therefore between their percentages, not between 500 and 270 L/s.


After repeated measured adjustments, assume the branch reaches A = 180, B = 270 and C = 450 L/s. Each terminal is at 90% of its own requirement, and the total is 900 L/s. The branch is now proportionally balanced in this example, but it still has a 100 L/s total shortfall. Record both facts. A uniform shortfall does not become an acceptable result merely because the ratios match.


4. Separate final flow trim from damper position


The ideal common airflow multiplier is design total/measured total = 1,000/900 = 1.111. Applying it to the balanced values gives 200, 300 and 500 L/s. This is the distribution target for the final trim. It is not an instruction to multiply every damper opening by 1.111, and it does not prove that increasing a fan-speed command by 11.1% will produce those exact site readings.


Three-stage example: initial flows 180, 240 and 580 L/s; proportional flows 180, 270 and 450 L/s; ideal final flows 200, 300 and 500 L/s.

Original hypothetical CAV branch. Matching 90% ratios establishes proportion; final measured adjustment must still deliver and verify the required total.


Damper position has a nonlinear relationship with resistance, and actual fan operation depends on the system and controls. A fan adjustment must remain within its approved operating limits. Use measured total flow and remeasure the terminals afterward. The 2023 ASHRAE Handbook—HVAC Applications, Testing, Adjusting, and Balancing chapter provides the broader measurement and air-balancing context. Do not replace the project method with a ratio-only calculation.


For a simple explanation of proportionality, approximate each fixed terminal path by pressure drop = R × airflow². If the paths share a common upstream pressure and downstream space pressure, airflow is proportional to the square root of that common pressure divided by R. Their airflow ratio can remain constant when the common pressure changes. That reasoning depends on unchanged resistances and boundaries; moving dampers, active controls, substantial leakage or changing room pressures can invalidate it.


5. Verify the final result and document exceptions


Assume the final readings after total-flow adjustment are A = 202, B = 296 and C = 502 L/s. Their total is exactly 1,000 L/s, but their deviations are +1.0%, −1.33% and +0.4%, respectively. Compare each result with the actual project tolerance. No universal tolerance is assumed here, and measurement uncertainty remains part of the review.


  • Keep design quantities, raw readings, correction factors and corrected flows traceable to the instrument and method.

  • Record initial ratios, significant intermediate scans and the final verified readings.

  • Confirm branch totals against an appropriate independent main or branch measurement, allowing for the measurement boundary and uncertainty.

  • Log unresolved restrictions or capacity deficiencies instead of hiding them in a reduced target.

  • Restore normal controls, then verify operation in the required modes.


To carry these readings into a consistent field record, the paid Air Balancing (TAB) Toolkit: Excel Workbook + Pocket Field Handbook combines percentage-of-design and deviation calculations with calibration checks, deficiency tracking and reporting. Its field handbook covers proportional balancing. Set its tolerance bands to the project requirements and retain the measured evidence supporting every adjustment.