Wraparound Heat Pipes: Separate Coil Duty from Recovered Heat

Oct 21
5 min read
Illustrative close view of finned heat-exchanger modules and copper return tubing.

Illustrative engineering scene. The worked calculation below uses explicit example inputs.


A wraparound heat pipe can reduce the cooling-coil duty needed to deliver dry, tempered air. A misleading selection comparison can also credit the same transferred heat twice. The reliable check is to label four air states, calculate each section on its own boundary, and then close the balance around the complete assembly.


One airstream, four measuring stations


In a wraparound arrangement, one module sits upstream of the cooling coil and another downstream. The first removes heat from incoming air; the second returns that heat to the cooled air. This is internal transfer along the same air path, not recovery from an independent exhaust stream. Trane describes the series arrangement, while Heat Pipe Technology specifies the paired locations for its dehumidifier heat pipes.




  • A: entering air, before the precool module.

  • B: precooled air, immediately before the cooling coil.

  • C: cold, dehumidified air leaving the cooling coil.

  • D: reheated air leaving the downstream heat-pipe module.


Keep the fan and any supplementary heater outside these boundaries initially. Assume steady operation, no leakage, negligible casing heat gain, and a dry upstream heat-pipe module. Humidity ratio therefore stays constant from A to B and from C to D; moisture removal occurs at the cooling coil.


Calculate the recovered heat once


Consider 1.50 kg/s of dry air at 101.325 kPa. The illustrative states are A = 30°C and 0.0140 kg/kg dry air, B = 25°C at the same humidity ratio, and C = 12°C and 0.0085 kg/kg. These are specified conditions for checking a balance, not a manufacturer selection.


Use moist-air enthalpy h in kJ/kg dry air, temperature T in °C, and humidity ratio w in kg/kg dry air:


h = 1.006T + w(2501 + 1.86T)


hA = 65.9752 kJ/kg


hB = 60.8150 kJ/kg


hC = 33.5202 kJ/kg


Internal transfer Qhp = 1.50 × (65.9752 − 60.8150) = 7.7403 kW


For the lossless heat-pipe balance, exactly 7.7403 kW returns between C and D. Use the downstream humidity ratio when converting that heat into a temperature rise:


TD = 12 + 7.7403 ÷ [1.50 × (1.006 + 1.86 × 0.0085)]


TD = 17.0501°C


hD = 38.6804 kJ/kg dry air


Precooling is 5.00 K, while reheat is 5.05 K. The slight difference follows from the different moist-air heat capacities before and after condensation; equal heat transfer need not produce identical temperature changes. Condensate production is 1.50 × (0.0140 − 0.0085) × 3600 = 29.7 kg/h.


Four air states pass through precool, cooling coil and reheat. One 7.740 kW arrow connects precool to reheat. Gross coil and net assembly airside duties are each 40.942 kW.

The wraparound heat pipe transfers 7.740 kW internally once. Under the stated boundaries, coil airside duty and net assembly cooling are both 40.942 kW.


Close the coil and assembly balances separately


Gross cooling-coil airside duty, B to C:


Qcoil = 1.50 × (60.8150 − 33.5202) = 40.9422 kW


Net assembly airside cooling, A to D:


Qnet = 1.50 × (65.9752 − 38.6804) = 40.9422 kW


Their equality is expected under these assumptions. The heat pipe takes 7.7403 kW out before the coil and puts it back afterward, so its contribution cancels across the whole assembly. Adding 7.7403 kW to the actual coil duty would describe A-to-C cooling, before the downstream reheat. It would not describe the air delivered at D.


Here, “gross” means the cooling coil’s airside enthalpy reduction before fan heat. For a precise refrigerant- or waterside balance, also account for energy leaving in liquid condensate. At an assumed 12°C drain temperature, that correction is about 0.414 kW, giving approximately 40.528 kW transferred to the cooling medium. Do not mix that corrected value with an uncorrected airside rating.


The double-credit error in a comparison


A conventional alternative cooling directly from A to the same C would require 48.6825 kW of airside cooling. A separate heater would then add 7.7403 kW to reach D. With the wraparound device, the coil duty falls by 7.7403 kW and the separate reheat requirement disappears at this operating point.


Correct cooling-coil reduction:


48.6825 − 40.9422 = 7.7403 kW


Incorrect reduced coil duty:


48.6825 − 7.7403 − 7.7403 = 33.2019 kW


The second subtraction treats avoided external reheat as another reduction in refrigeration duty. It understates the required coil duty by 7.7403 kW. Reporting both avoided cooling and avoided heating is legitimate when they remain separate services. Adding their thermal kW and calling the result an electricity reduction is not: cooling efficiency, heating source, operating hours, and added fan demand still have to be evaluated.


Delivered sensible cooling needs its own reference


The 40.9422 kW assembly result uses entering state A as its reference. If A is mixed outdoor and return air, that number includes ventilation conditioning and cannot simply be assigned to the rooms. Suppose the occupied space is at 24°C and w = 0.0100, with hroom = 49.6004 kJ/kg.


Room total cooling = 1.50 × (49.6004 − 38.6804) = 16.3800 kW


Room sensible cooling ≈ 1.50 × (1.006 + 1.86 × 0.0085) × (24 − 17.0501) = 10.6523 kW


The sensible expression uses supply-air humidity ratio for its heat-capacity convention. Both results exclude downstream fan and duct heat. A downstream fan heating the airstream reduces delivered cooling, even though it does not change the B-to-C coil measurement. Reheating also lowers relative humidity without lowering humidity ratio; a lower downstream RH reading alone does not demonstrate additional moisture removal.


Review the operating sequence, not just the design point


The example holds C fixed so the accounting is visible. Real coil capacity, leaving humidity and heat-pipe transfer interact. EnergyPlus models heat-exchanger-assisted coils by iterating the components toward a consistent leaving condition; a fixed recovery credit is therefore inadequate across changing airflow and entering conditions.



  • Request all four air states at design humidity, reduced sensible load, and minimum scheduled airflow. Confirm the complete assembly still meets the required supply temperature and humidity ratio.

  • State what controls moisture removal and what limits final supply temperature. Verify the selected equipment actually provides the necessary heat-pipe staging, modulation or bypass.

  • Check both modules’ pressure losses and the resulting fan selection. A thermally useful transfer does not establish net electrical savings.

  • Confirm whether the upstream module can condense moisture. If it does, replace the dry-module assumption with measured or selected humidity ratios and include its drainage in the water balance.


Heat Pipe Technology lists optional circuit controls and drainage arrangements; these are selection details to verify, not universal features to assume. During testing, trend temperatures and humidity ratios at the four stations together with airflow and control status. A mismatch between upstream removal and downstream addition should trigger checks for unstable operation, measurement error and heat leakage before a capacity claim is accepted.



Build a reviewable AHU selection


Keep internal transfer, gross coil duty, net assembly cooling and room delivery on separate lines of the review sheet. For a broader workflow covering AHU selection review, commissioning and diagnosis, the 182-page AHU Selection & Fault Diagnosis Handbook provides worked examples and practical checklists. Use it alongside, not instead of, manufacturer selections.



Continue the calculation review




Sources and calculation basis


Primary references checked on 21 October 2026. The worked examples and diagrams are original illustrative calculations, not manufacturer selections or project approvals. Apply the stated limitations and the requirements governing the actual project.