Dry Cooling-Coil UA Trending: Separate Temperature Driving Force from Deterioration

Illustrative engineering scene. The worked calculation below uses explicit example inputs.
An AHU cooling coil delivered 54 kW during a baseline test and only 36 kW during the next inspection. Calling that a 33% loss of coil performance would be premature. If the air entering the coil has become cooler while the entering water temperature remains unchanged, there is less temperature difference available to drive heat transfer.
A useful diagnostic separates three questions: did the thermal demand change, did either flow change, or did the heat exchanger itself deteriorate? Dry-coil effectiveness provides a first normalization. A model-based UA can then help compare similar operating points, provided its assumptions are visible. Neither calculation, by itself, proves fouling or identifies which surface needs attention.
Use this test only while the coil is genuinely dry
A dry coil removes sensible heat without condensing water from the air. EnergyPlus treats dry, wet and partly wet cooling-coil operation separately and uses different thermal calculations where condensation occurs. An entering-air dew point below the entering-water temperature is a useful dry-operation condition for a conventional water cooling coil.
For this example, entering air has a 10°C dew point and entering water is 15°C. Assume steady water-coil operation, no residual evaporation, no air bypass and negligible casing heat transfer. Do not reuse the dry-coil calculation for a humid-weather dehumidifying test. A temperature-only estimate would omit latent duty and could make a healthy wet coil look inconsistent.
Place air measurement planes immediately around the coil, without a fan or another coil between them. Measure a representative mixed temperature rather than one cold point behind a circuit. On the water side, use matched sensors and verify that the measured flow actually passes through this coil, not through a nearby bypass or common header.
Normalize with heat-capacity rates
Define each stream’s heat-capacity rate as its mass flow multiplied by its specific heat. Call these Ca for air and Cw for water, in kW/K. Select Cmin as the smaller value and Cmax as the larger. For a dry cooling coil, the maximum thermodynamic heat-transfer rate is Cmin multiplied by the entering-air minus entering-water temperature.
Qmax = Cmin × (Ta,in − Tw,in). Effectiveness ε = Qmeasured / Qmax. Also check Qa = Ca × (Ta,in − Ta,out) and Qw = Cw × (Tw,out − Tw,in). Reconcile Qa and Qw within the measurement uncertainty before interpreting ε.
The denominator uses two entering temperatures. It does not use the air temperature drop across the coil. Confusing those differences makes effectiveness equal to an arbitrary sensor ratio rather than the fraction of the available heat transfer actually achieved. Record which fluid is Cmin because that identity can change at different water flows.

Cooling can fall from 54 to 36 kW while effectiveness remains 0.6 and counterflow-equivalent UA remains 7.2984 kW/K.
Original comparison: three tests of one coil
Assume Ca = 6.00 kW/K and Cw = 9.00 kW/K in all three tests. These are stated example heat-capacity rates, not assumed volumetric flows. In a real test they must be calculated from independently established air and water mass flows, with appropriate fluid properties. Keep the same coil arrangement and fully open intended flow path.
Baseline: air enters at 30°C and leaves at 21°C; water enters at 15°C and leaves at 21°C. Qa = 6 × 9 = 54 kW and Qw = 9 × 6 = 54 kW. Qmax = 6 × (30 − 15) = 90 kW. Therefore ε = 54/90 = 0.600.
Mild-weather test: air enters at 25°C and leaves at 19°C; water enters at 15°C and leaves at 19°C. Both sides give 36 kW. Qmax = 6 × 10 = 60 kW, so ε remains 0.600. Duty fell by one third, but this normalized result shows no change.
Third test: retain 25°C entering air, 15°C entering water and both heat-capacity rates. Air now leaves at 20°C and water at 18.333°C. Both sides give 30 kW. Effectiveness is 30/60 = 0.500. This is a genuine departure from the earlier normalized result, subject to measurement validity.
The mild-weather result needs no corrective action merely because its kW value is smaller. The third test does justify investigation. Its observed deficit relative to the comparable second test is 6 kW, rather than the 24 kW difference obtained by comparing raw duty against the warmer baseline.
Convert effectiveness to an explicitly labelled model UA
UA combines overall heat-transfer coefficient and area. A value inferred from field temperatures depends on the chosen heat-exchanger model. For an illustrative counterflow model, define Cr = Cmin/Cmax and NTU = UA/Cmin. Rearranging the counterflow effectiveness relation gives the following calculation.
For Cr ≠ 1: NTU = ln[(1 − εCr)/(1 − ε)] / (1 − Cr). Here Cr = 6/9 = 0.6667. At ε = 0.600, NTU = 1.2164 and UA = 7.298 kW/K. At ε = 0.500, NTU = 0.8630 and UA = 5.178 kW/K.
Call these values counterflow-equivalent UA, not a certified physical rating of the installed coil. An actual finned-tube coil may require a crossflow or manufacturer-specific model. Use the same valid model for both tests. The inferred fall is about 29%, which differs from the 16.7% reduction in duty between the second and third tests because effectiveness is nonlinear in UA.
Investigate the changed boundary before ordering cleaning
ASHRAE’s coil treatment separates airside, tube-side and material thermal resistances. That structure matters when interpreting an apparent UA reduction: a changed overall result does not identify which resistance changed. Also, the sensible dry-coil model does not predict the moisture-removal process of a wet coil.
Recheck both flows. A valve command or fan-speed percentage is not independent evidence of flow.
Check sensor offsets and time alignment, particularly when the entering-temperature difference is small.
Confirm the coil stayed dry and the measurement period was long enough to avoid stored-water or casing transients.
Inspect for changed air bypass, blocked passages, uneven face velocity, air trapped in circuits or unintended water routing.
Repeat at a comparable stable operating point before assigning a maintenance cause.
A useful trend record retains the original temperatures, humidity, flows, valve and fan states, calibration notes, airside and waterside duties, and the normalized result. Store exclusions alongside the numbers. Rejecting an unstable or partly wet interval is more defensible than forcing every timestamp into a smooth deterioration curve.
For structured AHU fault investigation, get the complete AHU Selection & Fault Diagnosis Handbook. Its worked examples, fault cases and review checklists help organize the evidence before a corrective action is selected.
Continue the calculation review
Sources and calculation basis