Chilled-Water BTU Metering and Temperature-Sensor Accuracy

A dashboard can show a precise cooling-energy total while the measurements behind it remain uncertain. BTU metering combines flow with a small temperature difference, so sensor mismatch can distort the result, especially at low ΔT. Check the whole measurement chain before comparing performance or allocating costs.
Separate power from accumulated energy
A cooling meter evaluates heat transfer from the temperature rise between supply and return:
Q = ρ × V̇ × cₚ × (Tᵣ − Tₛ)
Here Q is thermal power in kW, ρ is density in kg/m³, V̇ is flow in m³/s and cₚ is specific heat in kJ/(kg·K). For water with ρ ≈ 1,000 and cₚ ≈ 4.18, 10 L/s at a 5 K difference gives 209 kW.
Energy = Σ(Q × Δt)
With time intervals in hours, the sum is kWh of cooling. A constant 209 kW for two hours gives 418 kWh thermal. This is not the electricity consumed by the plant. Configure the actual fluid and glycol concentration rather than applying water properties indiscriminately.
See why low ΔT exposes sensor error
Assume, solely for illustration, that each temperature channel has an error bounded by ±0.10 K. Opposite errors can make the measured difference wrong by ±0.20 K. Holding flow and fluid properties exact:
Relative temperature contribution = 0.20 ÷ ΔT × 100%
At a true 5 K difference, the worst-case contribution is 4%; at a true 2 K it is 10%. These are bounds for the example, not a claimed meter accuracy or statistical confidence interval. Flow, fluid-property and signal-processing errors still need consideration. Do not combine stated tolerance limits using root-sum-square unless their statistical meaning justifies it.
Specify and preserve the matched pair
Absolute temperature accuracy and differential accuracy are different requirements. Use a calibrated pair with documented performance over the operating range, and keep each sensor assigned to its intended meter and pipe. Replacing one sensor with an apparently identical spare can invalidate the pairing.
Confirm immersion, thermal contact, thermowell suitability and insulation using the manufacturer’s instructions. Avoid unequal installation conditions and unintended lead-wire changes. ONICON’s guidance explains why sensor matching and the intervening signal chain matter.

Temperature-error sensitivity with flow and fluid properties held exact. Illustrative channel error bounds, not a meter specification.
Give the flow meter a valid installation
Select a meter whose useful measuring range includes real part-load flow. Confirm pipe size, flow direction, a full pipe, air avoidance and the specified upstream/downstream conditions. Straight-length requirements vary with technology and nearby fittings; a generic pipe-diameter rule is insufficient.
Keep both temperature points and the flow measurement on the same energy boundary. Verify whether the meter is configured on supply or return. Belimo’s installation guidance shows why location and temperature-sensor assignment must agree.
Check the total before trusting the trend
Compare local readings with BAS values, including units, pulse factors, timestamps and accumulation intervals. Check sensor offsets at a common stable temperature, then verify performance across the operating range. Record calibration evidence, low-flow behavior and low-ΔT uncertainty. Cost-allocation or billing applications need the applicable contractual and metering requirements checked explicitly.
Put measurement into the design process