Glycol Refill Calculations: Include the Diluted Fluid Left in the System

A glycol system is partly drained for maintenance and then refilled with a premix labelled at the desired concentration. The final sample still reads low. That result is not necessarily an instrument fault: the stronger refill has mixed with weaker fluid left inside coils, low points and connected pipework. The concentration printed on the delivered container describes the addition, not the completed system.
A useful refill calculation starts with two inventories: the glycol already retained and the glycol required after filling. This article develops an original mass-balance example, including a batch-strength check and a simple uncertainty test. It does not choose the required freeze protection or authorize mixing products. Those decisions need the equipment and fluid suppliers’ requirements.
1. Put every concentration on the same basis
Write down the fluid identity, supplier formulation, concentration definition and reference temperature before entering quantities. “30%” can mean glycol by mass, commercial fluid by mass, or commercial fluid by volume. An inhibited commercial product contains other ingredients; a percentage of that product is not automatically the same percentage of pure glycol.
Dow’s FLUIDFILE calculator explicitly distinguishes volume percent fluid, weight percent glycol and weight percent fluid. Select the relevant basis rather than treating these options as interchangeable. The calculation below consistently tracks glycol mass fraction: glycol mass divided by total solution mass. All numbers are teaching assumptions, not a recommended concentration or branded product composition.
Mass is convenient because component masses add directly. If a delivery or a retained quantity is measured in litres, convert it using the applicable solution density at the recorded temperature: mass in kg = volume in L × density in kg/L. Use supplier mixture data when converting a volume-based concentration to a mass-based concentration; a density alone does not redefine what the original percentage measured.
2. Establish what remains after the drain
Assume an inventory survey and mass records establish that 1,200 kg of homogeneous solution remains after draining. Testing establishes a glycol mass fraction of 0.20. The retained glycol is therefore 1,200 × 0.20 = 240 kg. The retained fluid is treated as suitable for reuse following separate condition and compatibility review.
The intended final inventory is 2,000 kg at an approved target glycol mass fraction of 0.30. This final mass must represent the actual filled system at its reference condition. For example, an independently established working fluid volume of 1,923.08 L and an assumed target-mixture density of 1.040 kg/L give approximately 2,000 kg. These are illustrative inputs, not generic glycol properties.
A mass inventory is not the nominal volume printed on an expansion vessel. Count the fluid actually present in connected equipment and piping in the relevant fill state. Record any isolated sections separately. If the retained volume is uncertain, improve that estimate before placing confidence in a highly precise batch quantity.
3. Calculate the required refill strength
The final glycol inventory must be 2,000 × 0.30 = 600 kg. Since 240 kg is already retained, the addition must supply 360 kg of glycol. The total mass to add is 2,000 − 1,200 = 800 kg. Consequently, the required average glycol mass fraction of the refill is 360/800 = 0.45, or 45% by mass.
In general, let Mr be retained solution mass, wr its glycol mass fraction, Mf final solution mass and wt the target mass fraction. The refill mass is Mf − Mr, and its required fraction is wa = (Mf × wt − Mr × wr)/(Mf − Mr). The equation assumes no further fluid loss, no chemical change in the glycol inventory and complete mixing before the final result is evaluated.
Now test the tempting shortcut. Adding 800 kg of 30%-by-mass premix contributes only 240 kg of glycol. Final concentration becomes (240 + 240)/2,000 = 0.24, or 24% by mass. Using the correct target on the purchase order still leaves the system six percentage points below target because the retained charge was weaker.
4. Check whether the available stock can make that batch
Suppose the supplier approves a compatible stock solution containing 50% glycol by mass and suitable dilution water for this application. To supply the missing 360 kg of glycol, the batch needs 360/0.50 = 720 kg of stock. The remaining addition is 800 − 720 = 80 kg of water. Check both balances: 1,200 + 720 + 80 = 2,000 kg, and 240 + 0.50 × 720 = 600 kg glycol.

Original mass-balance example. Every concentration is glycol mass fraction. The 800 kg addition must average 45%, because the retained solution is only 20%.
If the only approved stock available is 40% by mass, 800 kg of it supplies 320 kg glycol. The final system would reach 28% by mass. A 45% addition cannot be made by diluting a 40% stock with water. That is a feasibility failure, not a rounding problem. Obtain an approved stronger supply or have the retained-fluid and drain/refill plan reconsidered.
For purchasing or metering, suppose the 50% stock density is an illustrative 1.060 kg/L at the transfer temperature. The required stock volume is 720/1.060 = 679.25 L. Do not order 720 L because the calculated quantity was 720 kg. Do not assume the separately measured liquid volumes add exactly to the final mixture volume; use the supplier’s mixing and density data.
5. Test sensitivity before relying on the result
Keep the 800 kg refill batch unchanged, but suppose the retained concentration was actually 18% rather than 20%. Final concentration becomes (1,200 × 0.18 + 360)/2,000 = 28.8%. If it was 22%, the result becomes 31.2%. A two-percentage-point uncertainty in this retained charge creates a 1.2-point uncertainty in the final concentration.
The general sensitivity here is Δwfinal = (Mr/Mf) × Δwretained. Since 60% of the final solution mass was retained, 60% of its concentration error carries into the result. This makes representative testing and the retained inventory more important than reporting the stock quantity to several decimal places.
Fernox’s refractometer guidance explains calibration, appropriate fluid scales and repeat readings. Use a method and conversion suitable for the actual formulation and concentration basis. An instrument displaying freeze temperature or a product percentage does not directly supply the glycol mass fraction required by this example without the appropriate conversion.
6. Close the refill record with measured evidence
The batch equation does not prove corrosion protection or fluid condition. Caleffi’s dilution guidance warns that excessive dilution can also weaken a formulated fluid’s inhibitor package. Have the supplier establish compatibility, water quality, target concentration and any required condition tests. Do not infer a universal minimum from this arithmetic example.
Record retained mass, sample locations, concentration basis and the source of each density.
Record the approved stock identity, actual delivered mass and water quantity.
After the approved mixing procedure, verify representative samples rather than relying on a single unmixed location.
Investigate continuing dilution or fluid loss before accepting repeated top-ups as normal.
Update the fluid-property basis used for hydraulic and equipment selections when the accepted mixture changes; review the glycol flow and equipment corrections on the same concentration basis.
The paid Chilled Water System Design Handbook connects piping, water treatment, equipment selection and commissioning through a structured PDF reference. Use this mass-balance record alongside that wider design workflow and the selected fluid supplier’s instructions. A refill is complete when the intended mixture is verified in the system, not simply when the planned containers are empty.