Occupied-Room CO₂: Check the Assumptions Before Inferring Outdoor Airflow

A room sensor reads 920 ppm CO₂. That number alone does not reveal the outdoor airflow. The same reading can arise from different populations, activity levels, outdoor backgrounds and ventilation histories. A defensible estimate starts with a defined occupied-room mass balance and then asks whether the observations support its assumptions. This article develops an inverse calculation and a field-data review, rather than a universal CO₂ target.
CO₂ does not demonstrate acceptable overall indoor air quality or complete ventilation-code compliance. ASHRAE’s 2025 Position Document on Indoor Carbon Dioxide explicitly limits what CO₂ can establish and emphasizes measurement quality and valid assumptions. Other contaminants, outdoor-air requirements, system distribution and the project’s adopted criteria require their own assessment.
1. Define the quantity that can be inferred
Use a simplified single, well-mixed zone with steady occupancy, constant occupant generation, constant outdoor background and constant outdoor-air exchange. Exclude combustion and other CO₂ sources, interzone transfer, material sorption and additional removal mechanisms. Assume dilute concentrations and a consistent temperature-and-pressure basis for gas-volume quantities. These exclusions are conditions to verify, not facts guaranteed by an ordinary room layout.
At steady state, source generation equals the excess CO₂ carried out by the exchanged air. If G is total CO₂ generation in L/s and Q is outdoor-air exchange in L/s, Q = 10⁶ × G/(Cin − Cout), with both concentrations in ppm by volume. The factor 10⁶ converts ppm to a volume fraction. Using ppm directly without that factor gives a millionfold unit error.
The NIST review of CO₂-based demand-controlled ventilation sets out the single-zone balance and steady-state relationship. Here Q represents exchange with the stated outdoor background. It is not automatically supply-fan airflow, measured mechanical intake or ventilation delivered to every occupied location. Infiltration can contribute to exchange, while transfer from another room requires an additional balance.
2. Work backward from an occupied plateau
Assume an original hypothetical test in a 360 m³ room. Twenty-four occupants remain at a stable activity level. Adopt an illustrative generation rate of 0.0050 L/s per person, expressed at the actual room operating conditions of 24°C and 101.325 kPa, also used for Q. Thus Q can be compared with the physical room volume when calculating air changes and the time constant. This is a calculation input, not a universal adult emission rate. Suppose representative simultaneous measurements have genuinely stabilized at Cin = 920 ppm and Cout = 420 ppm.
Total generation G = 24 × 0.0050 = 0.120 L/s of CO₂.
Indoor excess = 920 − 420 = 500 ppm.
Inferred outdoor exchange Q = 10⁶ × 0.120/500 = 240 L/s.
Per-person exchange = 240/24 = 10.0 L/s per person.
Volume conversion = 0.240 m³/s; outdoor air-change rate = 3,600 × 0.240/360 = 2.40 h⁻¹.
These values are mutually consistent within the model. They do not establish that 10 L/s per person is the required rate for this room. Nor can a 1,200 L/s supply reading be substituted for the 240 L/s outdoor exchange simply because the supply passes through an air filter. Ordinary particle filtration does not remove occupant-generated CO₂.
3. Test occupancy and source-rate sensitivity
If only twenty people were actually present, keeping the assumed per-person generation and measured 500 ppm excess gives G = 0.100 L/s and Q = 200 L/s. The estimate is 16.7% below the original 240 L/s. A design occupancy schedule is therefore not a substitute for the population during the measured interval.
With twenty-four occupants, changing the assumed per-person generation from 0.0050 to 0.0040 or 0.0060 L/s changes inferred flow to 192 or 288 L/s. These are sensitivity cases, not a statistically justified uncertainty interval. The input range must come from appropriate evidence before it can support a field conclusion.
Persily and de Jonge’s research on occupant CO₂ generation relates generation to occupant characteristics and activity. Do not copy a tabulated rate without its conditions. In particular, a CO₂ gas volume referenced to one temperature cannot be divided directly by an airflow referenced to another without conversion. Record the reference basis along with the numerical source rate.
4. Measure the outdoor background and examine the difference
Suppose outdoor CO₂ during the test was actually 500 ppm, while room CO₂ remained 920 ppm. The excess would be 420 ppm and the same assumed 0.120 L/s generation would imply 285.7 L/s. That is 19.0% above the estimate based on 420 ppm outdoors. A remembered outdoor value or a remote annual average is weak evidence for the simultaneous local background.

Original hypothetical steady-state inference. Generation is assumed to be 0.0050 L/s per person at the actual room conditions of 24°C and 101.325 kPa, also used for airflow. Results are model estimates, not required ventilation rates or an overall IAQ verdict.
Differential sensor error matters too. Starting from the original 500 ppm excess, an indoor error of +50 ppm combined with an outdoor error of −50 ppm produces a 600 ppm reported difference and an inferred 200 L/s. Reversing those errors produces 400 ppm and 300 L/s. These deliberately chosen error cases illustrate sensitivity; they are not the accuracy specification of a particular sensor or a complete uncertainty calculation.
Keep calibration information, sensor locations and timestamps. A sensor beside a person’s breathing zone or in a poorly mixed corner may report a real local concentration that is unsuitable as the zone-average input. When the indoor–outdoor difference is small, modest absolute errors can dominate the estimate. A zero or negative difference with a positive assumed source makes the simple positive-flow inference invalid.
5. A rising reading is not a steady-state reading
For the example’s 360 m³ and 0.240 m³/s, the ideal mixing time constant is V/Q = 1,500 s, or 25 minutes. If occupancy begins with room concentration equal to the 420 ppm outdoor background, the predicted concentration after fifteen minutes is 420 + 500 × [1 − exp(−15/25)] = 645.6 ppm. The final plateau remains 920 ppm.
Putting that early 225.6 ppm excess into the steady-state inverse equation would suggest about 532 L/s, more than twice the assumed true 240 L/s. After three time constants, this ideal case has reached about 95% of its final excess, not mathematical equilibrium. Changing occupancy or outdoor-air control can prevent a stable plateau altogether. The transient example explains a data-validity test; it is not a required universal waiting period.
6. Record a decision for each assumption
Population and activity stable and documented: retain the source estimate and its basis. Otherwise, classify the result as a scenario rather than a measured-flow conclusion.
Indoor and outdoor signals representative and synchronized: retain their difference and sensor evidence. Otherwise, resolve location or calibration limitations first.
A defensible plateau exists: document the trend interval. Otherwise, use an appropriate transient method or an independent airflow measurement.
Zone boundaries fit the model: record infiltration and interzone assumptions. Otherwise, obtain a more complete airflow and contaminant assessment.
For a broader calculation framework connecting outdoor-air requirements, air paths and controls, use the paid Ventilation Exhaust Design Practical Engineering Handbook. Its public scope includes ventilation calculations, replacement air and controls. Keep this CO₂ inference attached to its assumptions, and verify required outdoor airflow through the project’s accepted design and commissioning methods.