Cooling-Coil Face-and-Bypass Mixing: Meet Humidity as Well as Temperature

Oct 20
4 min read
A cooling coil, bypass damper and mixing plenum in an air-handling unit during isolated inspection.

An AHU reaches its supply-temperature setpoint, yet the space humidity keeps rising. One possible reason is the face-and-bypass arrangement: cold, dry coil air mixes with warmer air that did not pass through the coil. A temperature controller can find a satisfactory blend for sensible cooling without proving that the blend is dry enough.


That does not make every face-and-bypass system unsuitable. The design must establish which air is bypassed, what condition the coil branch can actually produce, and whether the mixed supply meets both temperature and moisture requirements. The useful calculation is an explicit two-stream balance, not a damper-position percentage.


1. Separate a real bypass path from coil bypass factor


A physical bypass duct or damper carries a real air stream around the cooling coil. Coil bypass factor is a simplified effectiveness representation used in coil analysis. It does not measure a physical leakage opening. Nexora’s coil bypass-factor and apparatus-dew-point guide explains that distinction and the limitations of the model.


For the present calculation, f means bypass dry-air mass flow divided by total dry-air mass flow. It is not actuator travel, blade angle, free-area fraction or necessarily the fraction of actual volumetric airflow. Branch temperatures and densities differ, and damper flow characteristics depend on the connected pressure paths.


Draw the split, the coil branch, the bypass branch and the mixing section. State whether the bypass carries mixed outdoor/return air or return air alone. Keep any fan heat, duct heat gain or downstream reheat outside the mixing boundary until the mixed state has been calculated.


2. Keep moisture and energy on the same basis


For adiabatic mixing with no liquid water exchange, humidity ratio is ws = (1 − f)wc + fwb. Enthalpy is hs = (1 − f)hc + fhb. Subscripts c, b and s identify coil leaving air, bypass air and mixed supply. Humidity ratio uses kg water per kg dry air, while enthalpy uses kJ per kg dry air.


Use h = 1.006T + w(2501 + 1.86T) for a conventional approximate moist-air enthalpy calculation with T in °C. Recover the mixed dry-bulb temperature from Ts = (hs − 2501ws)/(1.006 + 1.86ws). PsychroLib’s documented property functions provide a reproducible reference for moist-air enthalpy, humidity ratio and temperature conversions.


Do not average relative humidity. RH is temperature-dependent and does not obey the water-vapor mass balance. Also verify that the computed mixture is physically unsaturated at the project pressure. A supersaturated mixture requires a different treatment that accounts for condensation rather than accepting the algebraic result unchanged.


3. Original example: temperature passes, moisture fails


Assume a hypothetical AHU at 101.325 kPa, with total dry-air mass flow 2.00 kg/s. Air entering both paths is 26°C with humidity ratio 0.0130 kg/kg. At the stated operating point, assume the coil branch leaves at 11°C and 0.00750 kg/kg. These are invented, physically plausible selection inputs, not predictions of a particular coil.


The separately established supply requirements are approximately 16.3°C dry bulb and no more than 0.00900 kg/kg humidity ratio. The example does not derive that moisture requirement from occupancy or ventilation; it assumes the project’s zone moisture balance has already established it. Suppose 35% of dry-air mass bypasses the coil, so f = 0.35.


Coil-leaving enthalpy is 29.977 kJ/kg and bypass enthalpy is 59.298 kJ/kg. The mixture has ws = 0.65 × 0.00750 + 0.35 × 0.0130 = 0.009425 kg/kg. Its enthalpy is hs = 0.65 × 29.977 + 0.35 × 59.298 = 40.239 kJ/kg, retaining unrounded values internally.


The recovered supply temperature is 16.28°C, effectively the assumed 16.3°C target at normal reporting precision. However, the supply contains 9.425 g/kg rather than the permitted 9.000 g/kg. At 2.00 kg/s, the excess relative to that supply target is 2.00 × 0.000425 × 3600 = 3.06 kg/h of water vapor. A temperature-only acceptance test would miss it.


4. Solve the moisture-limited bypass fraction


Original face-and-bypass balance: 35 percent bypass produces 16.28°C supply at 9.425 g/kg, above the 9.000 g/kg target; limiting bypass to 27.3 percent yields 15.12°C at 9.000 g/kg under fixed branch-state assumptions.

Original assumed dry-air mass balance. The computed 27.3% limit requires the stated coil leaving condition to remain achievable at the increased coil-branch flow.


If the two branch states were maintained, the largest acceptable bypass fraction would be fmax = (ws,max − wc)/(wb − wc). Here it equals (0.00900 − 0.00750)/(0.0130 − 0.00750) = 0.2727, or about 27.3% of total dry-air mass.


At that blend, mixed humidity ratio is exactly 0.00900 kg/kg and mixed enthalpy is 37.974 kJ/kg. The resulting dry bulb is 15.12°C. The humidity-limited blend is therefore colder than the approximately 16.3°C sensible target. In this assumed case, bypass alone cannot deliver both targets using the stated branch conditions.


Heating that mixed air from 15.12°C to 16.3°C at unchanged humidity ratio would require 2.00 × (1.006 + 1.86 × 0.00900) × (16.3 − 15.12) ≈ 2.41 kW. That is a calculated tempering duty, not automatic permission to install or enable reheat. Review applicable energy requirements, available heat sources and the complete control architecture.


5. Do not freeze the coil leaving condition during reselection


Reducing bypass from 35% to 27.3% increases the coil-branch dry-air flow from 1.30 to 1.455 kg/s. A real coil may not continue producing 11°C and 7.50 g/kg at that higher flow. The preceding result is a feasibility screen with stipulated branch states. Request a revised manufacturer selection or measure the new states before accepting it as an operating prediction.


Trane’s dehumidification discussion distinguishes mixed-air bypass from return-air bypass and explains why routing humid outdoor air through the coil can improve performance. Its historical discussion supports the configuration distinction, not a universal guarantee or current code conclusion. A return-air bypass arrangement still needs its own complete mass balance and ventilation verification.


6. Turn the calculation into a field decision


  • Measure temperature and humidity in both branches and after a representative mixing section, using synchronized, suitable instruments.

  • Establish branch mass flow rather than translating damper command directly into a bypass percentage.

  • Check seals, linkage, coil water conditions and available coil face area against the actual configuration.

  • Test a credible low-sensible, high-moisture condition, not only the peak cooling duty.


If the mixed supply meets temperature but exceeds its moisture target, the next action is to reconcile branch states and the allowed bypass fraction. Blindly lowering the room thermostat does not establish the missing latent performance. Likewise, adding downstream heat changes dry bulb but does not remove the extra moisture from an already too-wet blend.


For a structured review of the wider unit and humidity sequence, the paid AHU Selection & Fault Diagnosis Handbook covers psychrometrics, cooling coils, controls and selection review. Use its broader workflow alongside a project-specific mixing calculation and verified manufacturer data, rather than treating a satisfactory temperature trend as proof of dehumidification.