top of page

Dehumidification Using Cooling Coils (Calculation Guide)

Updated: 2 days ago

Introduction


Dehumidification Using Cooling Coils

Dehumidification using cooling coils is one of the most important psychrometric processes in HVAC design, especially in hot and humid climates, hospitals, laboratories, commercial buildings, and ventilation systems with high outdoor air fractions. Engineers often face a practical challenge: a cooling coil may reduce air temperature, but unless the coil surface temperature is below the entering air dew point, it will not remove enough moisture.

In real projects, this issue directly affects indoor comfort, mold risk, condensation control, occupant health, and equipment reliability. A system may appear to have enough total cooling capacity, yet still fail to maintain indoor relative humidity because the latent load was underestimated or the cooling coil was selected only for sensible cooling.

This guide explains how dehumidification using cooling coils works, how to calculate moisture removal, and how engineers use psychrometrics, apparatus dew point, and bypass factor to evaluate coil performance. (Dehumidification Using Cooling Coils)

Definition :

Dehumidification using cooling coils is the HVAC process in which moist air is cooled below its dew-point temperature so that water vapor condenses on the coil surface. The air loses both sensible heat and latent heat, resulting in lower dry-bulb temperature and lower humidity ratio.



Read related topic :


What is Dehumidification Using Cooling Coils

A cooling coil in an air handling unit, rooftop unit, or fan coil unit is designed to transfer heat from air to chilled water or refrigerant. When the coil surface is cold enough, two processes occur at the same time:

  • Sensible cooling: air temperature decreases

  • Latent cooling: moisture condenses and is removed from the air stream


System purpose (Dehumidification Using Cooling Coils)

The main purpose is to control both temperature and humidity in the conditioned space or in the supply air stream.


Where it is used

Cooling coil dehumidification is commonly applied in:

  • comfort air conditioning systems

  • dedicated outdoor air systems

  • hospitals and clean spaces

  • museums and archives

  • food processing facilities

  • basements and underground spaces

  • schools and commercial offices in humid regions


Why engineers apply it

Engineers use this process because indoor humidity that is too high can lead to:

  • microbial growth

  • discomfort at otherwise acceptable temperatures

  • condensation on diffusers, ducts, and glazing

  • reduced indoor air quality

  • instability in process-controlled spaces


Engineering Principles

Dehumidification using cooling coils is governed by psychrometrics, heat transfer, and mass transfer.


1. Dew point and condensation

Condensation begins when the air contacting the coil surface is cooled below its dew point. If the coil surface temperature remains above the dew point, no moisture removal occurs.


2. Sensible and latent heat transfer

The coil removes total heat from the air:

Total Heat = Sensible Heat + Latent Heat

  • Sensible heat changes dry-bulb temperature

  • Latent heat removes moisture by phase change


3. Humidity ratio

The humidity ratio, usually expressed in kg water/kg dry air, is the main property used to quantify moisture removal. The difference between entering and leaving humidity ratio determines condensate rate.


4. Apparatus Dew Point (ADP)

The ADP is the effective coil surface temperature at which the process line on the psychrometric chart would intersect the saturation curve. It represents the coil condition required to produce the leaving air state.


5. Bypass Factor (BF)

Not all air contacts the coil surface equally. Some portion effectively bypasses full treatment. The coil bypass factor is:


BF = (t_leave - t_ADP) / (t_enter - t_ADP)


A lower bypass factor means better contact and stronger dehumidification.


6. Sensible Heat Ratio (SHR)

SHR indicates how much of the total coil load is sensible:


SHR = Sensible Heat / Total Heat


A low SHR means stronger latent performance, which is important in humid applications.

Step-by-Step Engineering Process


Step 1 – Determine entering air conditions

Establish the entering dry-bulb temperature and relative humidity, or use dry-bulb and wet-bulb values. From the psychrometric chart or software, determine:

  • humidity ratio

  • enthalpy

  • dew point

Example entering air condition:30°C DB, 60% RH

Approximate properties:

  • humidity ratio, W1 ≈ 0.016 kg/kg

  • enthalpy, h1 ≈ 71 kJ/kg

  • dew point, approximately 21.4°C


Step 2 – Define leaving air condition

Assume or calculate the leaving air state based on required supply conditions or selected coil performance.

Example leaving air condition:14°C saturated air

Approximate properties:


  • humidity ratio, W2 ≈ 0.010 kg/kg

  • enthalpy, h2 ≈ 39 kJ/kg


Because the leaving air is saturated, the coil is clearly performing both cooling and dehumidification.


Step 3 – Calculate moisture removal

Moisture removed from the air is based on the reduction in humidity ratio:

ṁwater = ṁair × (W1 - W2)

Where:

  • ṁwater = condensate removal rate, kg/s

  • ṁair = dry air mass flow rate, kg/s

  • W1, W2 = entering and leaving humidity ratio, kg/kg dry air


If air flow rate is 2.5 kg/s:

ṁwater = 2.5 × (0.016 - 0.010) = 0.015 kg/s


That equals:

  • 0.9 kg/min

  • 54 kg/h


This is the actual dehumidification rate of the coil.


Step 4 – Calculate coil cooling load

The total cooling load across the coil is:

Q_total = ṁair × (h1 - h2)

Using the example:

Q_total = 2.5 × (71 - 39) = 80 kW


Then estimate sensible load:

Q_sensible = 1.02 × ṁair × (T1 - T2)


Using SI air-side approximation:

Q_sensible = 1.02 × 2.5 × (30 - 14) = 40.8 kW


Then latent load is:

Q_latent = Q_total - Q_sensible = 80 - 40.8 = 39.2 kW


This shows nearly half the coil load is latent, which is common in humid outside air applications.


Read related topic :


Practical Engineering Example

Consider a fresh air handling unit serving a lobby in a coastal climate.


Design data:

  • Outdoor air: 32°C DB, 24°C WB

  • Supply air after coil: 13°C saturated

  • Dry air flow rate: 3.0 kg/s


Approximate psychrometric properties:

  • Entering humidity ratio, W1 ≈ 0.0185 kg/kg

  • Entering enthalpy, h1 ≈ 79 kJ/kg

  • Leaving humidity ratio, W2 ≈ 0.0093 kg/kg

  • Leaving enthalpy, h2 ≈ 36 kJ/kg


Moisture removal

ṁwater = 3.0 × (0.0185 - 0.0093) = 0.0276 kg/s

That is:

  • 1.66 kg/min

  • 99.4 kg/h


Total coil load

Q_total = 3.0 × (79 - 36) = 129 kW


Sensible load

Using 32°C to 13°C:

Q_sensible = 1.02 × 3.0 × (32 - 13) = 58.1 kW


Latent load

Q_latent = 129 - 58.1 = 70.9 kW


Engineering interpretation

This coil is performing significant dehumidification because:

  • leaving air is near saturation

  • coil surface temperature is below entering dew point

  • latent load is greater than half the total load

In practice, this would require proper condensate drain design, corrosion-resistant materials in coastal regions, and careful control valve sequencing to avoid humidity drift at part load.

Technical Comparison Table

Parameter

Sensible Cooling Only

Cooling with Dehumidification

Coil surface temperature

Above air dew point

Below air dew point

Dry-bulb temperature

Decreases

Decreases

Humidity ratio

No significant change

Decreases

Condensate formation

No

Yes

Latent heat removal

Negligible

Significant

Supply air RH

May remain high

Usually near saturation at coil leaving

Best application

Dry climates or low latent loads

Humid climates or high ventilation loads

Drain pan required

Not critical

Essential

Psychrometric path

Horizontal left

Downward left

Risk if misapplied

High indoor humidity

Possible overcooling if not controlled

Advantages

Cooling coil dehumidification offers several engineering benefits:

  • provides combined temperature and humidity control

  • supports ventilation air pretreatment

  • reduces indoor condensation risk

  • improves comfort in humid climates

  • helps maintain IAQ and building durability

  • works with chilled water or DX systems

  • integrates well with AHUs, DOAS, and packaged systems

For many commercial buildings, it is the most practical and economical first-stage humidity control method.


Read related topic :


Common Engineering Mistakes

Engineers often run into performance problems because of avoidable design assumptions.


1. Ignoring latent load

Sizing a coil only from room sensible load can lead to under-dehumidification.


2. Using dry-bulb temperature alone

Air leaving temperature does not tell the full story. Humidity ratio and enthalpy must also be checked.


3. Assuming the coil leaving air is always saturated

Real coils may have a nonzero bypass factor. Leaving air may not be exactly on the saturation curve.


4. Not checking apparatus dew point

Without ADP evaluation, the selected coil may not achieve the required moisture removal.


5. Poor condensate management

Improper drain slope, trap design, or pan insulation can create water carryover and hygiene issues.


6. Part-load control problems

At reduced chilled water flow or high supply air temperature reset, the coil may lose latent capacity.


Future Trends

Cooling coil dehumidification is evolving with better controls and digital system integration.


Smart latent control

Modern BAS platforms increasingly monitor dew point, humidity ratio, and coil valve position instead of relying only on dry-bulb control.


Dedicated outdoor air systems

DOAS units are becoming more common because they separate ventilation latent treatment from zone sensible conditioning.


AI-assisted optimization

Advanced analytics can predict when a coil is drifting from expected latent performance due to fouling, valve issues, or sensor error.


Digital twin integration

Digital twins allow facility teams to compare expected and actual coil behavior, including moisture removal and condensate trends.


High-performance coils

Improved fin geometry, lower bypass factor designs, and better hydrophilic coatings can increase latent capacity while reducing pressure drop.


FAQ Section


1. When does a cooling coil start dehumidifying air?

A cooling coil starts dehumidifying when its effective surface temperature drops below the dew-point temperature of the entering air.


2. How do you calculate moisture removed by a cooling coil?

Use the dry air mass flow rate multiplied by the difference between entering and leaving humidity ratio:ṁwater = ṁair × (W1 - W2)


3. Why is leaving air often close to saturation?

Because air in direct contact with the cold coil surface approaches the apparatus dew point, which lies on or near the saturation line.


4. What is the role of bypass factor in coil calculation?

Bypass factor shows how much air is not fully treated by the coil. Lower bypass factor means colder leaving air and better dehumidification.


5. Can a coil provide humidity control at part load?

Yes, but only if the control strategy maintains sufficiently low coil temperature. Otherwise the system may satisfy sensible load while failing to remove latent load.


Read related topic :


Conclusion

Dehumidification using cooling coils is more than a temperature reduction process. It is a combined sensible-latent treatment that depends on dew point, humidity ratio, enthalpy difference, apparatus dew point, and coil bypass factor. For accurate HVAC design, engineers must evaluate both total cooling and moisture removal instead of relying on dry-bulb temperature alone.

In humid buildings and outdoor air systems, a well-selected cooling coil can remove large amounts of water vapor while maintaining stable supply air conditions. The key calculation steps are straightforward: determine entering and leaving psychrometric properties, calculate humidity ratio difference, estimate condensate rate, and verify total, sensible, and latent load performance.


Author Note :

Nexora Design Lab publishes engineering insights on HVAC design, MEP systems, and sustainable building technologies used in modern construction projects.


Subscribe to our blog page for more.....


Comments

Rated 0 out of 5 stars.
No ratings yet

Add a rating
bottom of page