Duct Leakage at Operating Pressure: Convert Each Tested Section Before Adding

Three duct sections record 60, 40 and 30 L/s of leakage during isolated pressure tests. Adding them gives 130 L/s, but that sum does not automatically describe leakage while the AHU is running. The sections may have been tested at different pressures, and their operating pressures can differ substantially along the network. A useful operating estimate preserves each section’s measured leakage and pressure before applying a stated pressure model.
This article develops that translation for ordinary comfort-HVAC ductwork. Formal test acceptance remains a separate decision under the project specification. Nexora’s duct leakage test acceptance guide covers tested area, class, units and reporting. Here the question is what a valid sectional result can reasonably tell the designer about a defined operating mode.
1. Start with the pressure across the duct wall
Leakage is driven by the pressure difference between the air inside the duct and the surrounding space. For a supply duct in a ceiling void, use the internal static pressure relative to that void. Fan total pressure includes a different boundary and is unsuitable as a universal leakage pressure. A duct passing through spaces at different pressures may need additional subdivision.
Record the sign separately from the magnitude. Positive internal pressure drives outward leakage; negative internal pressure can draw surrounding air inward. Raising a negative number to a fractional power is not the intended calculation. Supply loss and return-side infiltration also have different consequences, so keep their balances separate rather than subtracting one from the other and calling the system tight.
The 2024 SMACNA duct and system leakage presentation hosted by Connecticut ASHRAE explains the pressure-dependent leakage relationship and distinguishes ductwork from accessories and equipment. Keep those boundaries on the drawing. A duct-only specimen cannot establish the leakage of an AHU casing, terminal box or damper that was excluded from its test.
2. Use a pressure ratio with an explicit exponent
For an unchanged specimen, a useful engineering model is Q = C × |Δp|^n. Q is leakage flow, C represents the specimen’s leakage characteristics, and n is the assumed or measured pressure exponent. If the same model applies at both pressures, dividing the two equations eliminates C: Qoperating = Qtest × (|Δpoperating| / |Δptest|)^n.
The pressure ratio is dimensionless. Both pressures may be in pascals, or both in inches water gauge, but they must use the same unit. The flow result retains the unit of Qtest. Do not import a leakage-class coefficient from a different unit convention into this ratio calculation.
Use n = 0.65 only as the declared model for the example below. The TSI PAN341 operating manual, Appendix B summarizes pressure-power leakage relationships used in duct testing. A conventional exponent is not evidence that a particular damaged joint, flexible connection or moving seal follows that exponent over every pressure range. Multiple valid test points can support a fitted exponent when the procedure permits.
3. Worked example: three separately tested supply sections
Assume three nonoverlapping duct-only sections with unchanged seals after testing. All leakage readings use a common volume-reference basis, with comparable air conditions and no additional density correction required for this illustration. Local operating pressures are representative steady values relative to the surrounding void. The model neglects the distribution of pressure within each section.
Section A: measured leakage 60.0 L/s at +500 Pa; representative operating pressure +300 Pa.
Section B: measured leakage 40.0 L/s at +500 Pa; representative operating pressure +120 Pa.
Section C: measured leakage 30.0 L/s at +300 Pa; representative operating pressure +60 Pa.

Original pressure-model example with n = 0.65, unchanged test boundaries and a common airflow-reference basis. Local operating pressure is the duct-to-surroundings static difference. These estimates do not replace test acceptance or TAB.
Using n = 0.65, section A gives 60.0 × (300/500)^0.65 = 43.05 L/s. Section B gives 40.0 × (120/500)^0.65 = 15.82 L/s. Section C gives 30.0 × (60/300)^0.65 = 10.54 L/s. The combined operating estimate is 43.05 + 15.82 + 10.54 = 69.41 L/s, using unrounded intermediate values.
Suppose the common-basis supply flow entering this complete three-section boundary is 5,000 L/s. Estimated duct leakage is 69.41/5,000 × 100 = 1.39% of that entering flow. With no other losses or outlets outside the accounted terminal set, the ideal balance leaves approximately 4,930.59 L/s at the terminals. This is a boundary-specific estimate, not a measured TAB result.
Simply adding the raw tests would give 130 L/s, or 2.60%. Applying +300 Pa to every section would instead give 101.75 L/s. Both shortcuts discard the stated operating-pressure distribution. The calculation is improved by preserving location, although its accuracy still depends on how well each representative pressure describes the leakage sites.
4. Keep operating uncertainty visible
A single measured leakage point cannot determine both C and n independently. To show sensitivity, repeat the example with n = 0.50 and n = 0.80 while keeping the same test readings and operating pressures. These illustrative alternatives produce approximately 79.49 and 60.92 L/s respectively. They are scenario bounds chosen for this calculation, not measured confidence limits or acceptance tolerances.
If pressure varies appreciably within section A, a single average may be inadequate. The better model divides that section into smaller areas with defensible leakage coefficients and local pressures, then sums their leakage. An arithmetic average pressure is not automatically the correct effective pressure for a nonlinear relationship, particularly when poor joints are concentrated at one end.
Record the flow-reference basis as carefully as the pressure basis. The TSI PAN341 product documentation describes automatic correction to standard conditions. A corrected test reading and an actual operating fan volume must be reconciled before expressing leakage as a percentage. Avoid applying a second correction to data already normalized by the instrument.
5. Recalculate the percentage at VAV turndown
Assume the boundary’s supply flow falls to 2,500 L/s and, for a deliberately simplified comparison, every local pressure also falls to half its previous value. The modeled leakage becomes 69.4061 × 0.5^0.65 = 44.23 L/s. Absolute leakage falls, but its share of entering flow rises to 44.23/2,500 × 100 = 1.77%.
If instead the relevant local pressures remain unchanged while supply flow halves, the same model retains 69.41 L/s leakage, now 2.78% of entering flow. These are two different control scenarios. A VAV system does not guarantee either pressure pattern merely because total airflow has changed. Obtain operating pressures for the intended control mode, including the effect of static-pressure reset and terminal throttling.
This also explains why a single fixed leakage percentage can mislead a part-load analysis. The pressure field and the denominator both change. Do not infer fan energy savings by multiplying the leakage reduction by fan rated power; the fan curve, control response, pressure requirement and efficiency must be evaluated separately.
6. Turn the estimate into a reviewable schedule
Retain one row per test boundary, with test pressure and direction, measured leakage, reference conditions, assumed exponent, operating pressure, operating mode and calculated leakage. Mark excluded equipment and untested sections. Identify whether each operating pressure came from measurement, a network calculation or a preliminary assumption.
Revisit the estimate after significant routing changes, repairs or control modifications. Use actual airflow measurements to check the final operating balance, recognizing measurement uncertainty and all included branches. Never reduce a required test pressure or declare a failed specimen acceptable because its calculated operating leakage is lower.
To organize the associated section-by-section duct calculation, use the paid HVAC Duct Pressure Loss Design Suite. Its section schedules, friction and fitting-loss calculations, critical-path review and fan-ESP reports support a traceable network assessment. Attach this separately checked leakage schedule to that work; the public product description does not claim an operating-leakage converter.