Ventilation Purge Time: Calculate Concentration Decay Above Outdoor Background

A room receives its own volume of outdoor air every twenty minutes. It is tempting to conclude that twenty minutes completely replaces the original room air. In an ideal continuously mixed room, however, incoming air mixes with the air already present while an equal volume leaves. Some of the newly supplied air also exits, and the original excess concentration decays gradually.
This article uses a hypothetical nonreactive tracer to explain ordinary ventilation calculations. Its illustrative concentrations and reduction targets are mathematical inputs, not exposure limits or instructions to release a substance. The calculation cannot establish safe re-entry, hazardous-atmosphere clearance, infection-control clearance or smoke-purge compliance. Those applications require their own qualified assessment and procedures.
1. Define a single-zone mass balance
Let V be the fixed, well-mixed room volume in m³; Q be the effective outdoor-air exchange flow in m³/s; C be room concentration in mg/m³; Cout be the constant incoming outdoor concentration; and G be a source rate in mg/s. With equal inflow and outflow, no reaction, deposition or filtration, the mass balance is V × dC/dt = G + Q × Cout − Q × C.
Every term has units of mg/s. This unit check helps distinguish a source rate from a concentration and prevents an airflow in m³/h from being combined with time in seconds. The definition of Q is especially important: for this model it is the exchange with the specified background air, not automatically the AHU supply flow.
The NIST CONTAM documentation describes more general airflow and contaminant balances, including interzone transport, sources and removal mechanisms. The single-room equation here deliberately leaves those additional mechanisms out. Make that simplification explicit before interpreting its output.
2. Solve the source-off case above background
When the source has stopped, G = 0. Define excess concentration X = C − Cout. For constant Q and V, the solution is X(t)/X(0) = exp(−Q × t/V). If n = 3,600 × Q/V is the outdoor air-change rate in h⁻¹, the same relationship is X(t)/X(0) = exp(−n × t/60), with t in minutes.
The time to reach a chosen remaining fraction f is t = −60 × ln(f)/n minutes. Use the natural logarithm. For 90% removal of the initial excess, f = 0.10; for 99%, f = 0.01. These percentages refer to excess above the incoming background, which is why the background must remain in the final concentration calculation.
At one nominal air change, Q × t/V = 1. The remaining fraction is exp(−1) = 0.3679, or 36.79%. Thus the initial excess has fallen by 63.21%. The result follows from the mixing model; a nominal air change does not mean that each original parcel has exited exactly once.
3. Worked example: supply flow and outdoor exchange differ
Assume a 600 m³ room served by a system supplying 2.00 m³/s. Of that supply, 0.50 m³/s is outdoor air and 1.50 m³/s is recirculated room air. Assume balanced exchange, no other zones or infiltration, constant density, instant uniform mixing and no tracer removal in the recirculation path. The source has stopped at time zero.
The total supply air-change rate is 3,600 × 2.00/600 = 12 h⁻¹. The effective outdoor exchange rate for this tracer is only 3,600 × 0.50/600 = 3 h⁻¹. Recirculation helps move and mix air, but in this assumed system it returns the tracer rather than removing it. NIST’s discussion of ventilation measurement methods and metrics stresses the importance of relating measured supply, intake and exhaust flows to the actual ventilation arrangement.
Set the hypothetical initial concentration to 102 mg/m³ and the outdoor background to 2 mg/m³. Initial excess is 100 mg/m³. A 90% excess reduction means a remaining excess of 10 mg/m³, giving a target room concentration of 12 mg/m³. Using n = 3 h⁻¹, t90 = −60 × ln(0.10)/3 = 46.05 minutes.
For 99% excess reduction, the target is 2 + 1 = 3 mg/m³ and t99 = 92.10 minutes. At the twenty-minute time constant, C = 2 + 100 × exp(−1) = 38.79 mg/m³. Each result uses the same mass balance and the same background.

Original ideal well-mixed, source-off example. Background is 2 mg/m³ and initial concentration 102 mg/m³. Three outdoor air changes per hour govern the decay; untreated recirculation is excluded. This is not a safety-clearance calculation.
If someone substitutes the 12 h⁻¹ total supply rate, the calculated 90% time becomes 11.51 minutes, four times shorter. That answer assumes all supply air removes tracer as effectively as the specified outdoor stream. It contradicts the example’s untreated recirculation boundary.
4. Account for changing flow without averaging carelessly
For a source-free, well-mixed room with constant background but variable Q, the remaining fraction is exp[−∫Q(t)/V dt]. In a practical piecewise-constant worksheet, add each interval’s air-change exposure: sum(nᵢ × Δtᵢ/60), with intervals in minutes. The necessary exposure for 90% reduction is −ln(0.10) = 2.302585.
Suppose the room operates at 3 h⁻¹ for the first twenty minutes, then outdoor flow doubles to 1.00 m³/s, giving 6 h⁻¹. The first interval contributes 3 × 20/60 = 1.00. The remaining exposure is 2.302585 − 1.00 = 1.302585, requiring 60 × 1.302585/6 = 13.03 additional minutes. Total ideal time is 33.03 minutes.
This calculation uses achieved outdoor flow in each interval. A controller command alone is insufficient evidence. Nexora’s minimum outdoor-air verification guide explains why damper position cannot establish that flow. Include fan startup and stabilization, and do not count time at design flow before the measured flow reaches it. If the source, background or mixing state changes, integrate the appropriate mass balance rather than applying this simpler source-off expression.
5. An ongoing source changes the destination
With constant G, Q and Cout, the equilibrium concentration is Ceq = Cout + G/Q. The transient becomes C(t) = Ceq + [C(0) − Ceq] × exp(−Q × t/V). The room approaches Ceq instead of approaching the outdoor background.
Return to Q = 0.50 m³/s, V = 600 m³ and Cout = 2 mg/m³. If a hypothetical source continues at 5.0 mg/s, G/Q = 10 mg/m³ and Ceq = 12 mg/m³. The earlier 12 mg/m³ target is now the equilibrium itself: starting above it, the ideal curve approaches that value but does not reach it in any finite time. Simply adding ten minutes to the source-off purge time cannot fix that mathematical mismatch.
A continuing source might also be time-varying, such as material release that declines slowly. Filtration, adsorption and deposition can matter for some substances, but their effectiveness is substance-specific. Do not count a particle filter as removal for an arbitrary gas or apply one clean-air rate to every contaminant. A richer model needs supported source and removal inputs.
6. Test whether the room behaves like the model
Short-circuiting between supply and exhaust, poorly mixed recesses and exchange with adjacent rooms can produce different local decay histories. NIST’s test-chamber ventilation study illustrates the importance of concentration uniformity and representative sampling locations. A sensor next to a clean supply jet can indicate a rapid decline while another location remains elevated.
For a legitimate ventilation investigation, qualified personnel should define the measurement method, instrument range and accuracy, sample locations, background monitoring and required operating stability. This article does not prescribe a tracer-release test. When reviewing existing data, retain timestamps and room/system configuration so that a repeat comparison has meaning.
Close the calculation with its assumptions: room volume, measured outdoor exchange, initial and background concentrations, source status, reduction target and evidence supporting mixing. For the wider airflow and exhaust-design workflow, use the paid Ventilation Exhaust Design Practical Engineering Handbook. Its ventilation airflow, makeup-air, duct-loss and fan-selection examples support system planning; use a separately checked decay calculation for this transient question.