How to Calculate the Correct Condensate Trap for Negative-Pressure AHUs
Updated: 2 days ago
In a draw-through AHU, the cooling coil and drain pan are usually located upstream of the supply fan. Because the fan is pulling air through the coil section, the drain pan area operates under negative static pressure. This negative pressure tries to pull air upward through the condensate drain pipe, which can stop water from draining properly.
If the condensate trap is undersized, the AHU may suffer from water carryover, overflowing drain pans, microbial growth, ceiling leakage, and nuisance maintenance complaints. A correctly sized trap is therefore not a small plumbing detail; it is part of proper AHU design.
1. What Is a Negative-Pressure Condensate Trap?
A condensate trap is a water seal installed in the drain line from the AHU drain pan. Its purpose is to prevent air from being sucked into the AHU through the drain pipe and to allow condensate water to discharge freely.
In a negative-pressure AHU, the pressure inside the drain pan is lower than atmospheric pressure. Without a proper trap, the fan suction can hold the water inside the drain pan and prevent drainage. (How to Calculate the Correct Condensate Trap for Negative-Pressure AHUs)
Common examples include:
Draw-through AHUs
FCUs with fan after the coil
Packaged units with negative-pressure drain pans
Fresh air handling units with cooling coils before the fan

Download the full design guide PDF with detailed calculations, sizing, code compliance, and real project insights. (How to Calculate the Correct Condensate Trap for Negative-Pressure AHUs)
For detailed calculations, project-specific design, and authority-compliant solutions, contact our engineering team.
Email : info@nexoradesign.net
Phone : +94 76 720 5408
Web : www.nexoradesign.net
Read related blogs
AHU Drain-Pan Design: Slope, Trap Depth and Overflow Protection
How to Select an AHU Cooling Coil: Rows, Fins and Face Velocity
HVAC Water Treatment: Preventing Scale, Corrosion and Biological Growth
Hydraulic Decoupling in Chilled-Water Plants Explained
How Air and Dirt Separators Improve Chilled-Water Performance
Automatic Balancing Valves vs Manual Balancing Valves: Which Is Better for HVAC Hydronic Systems?
Sizing pipework on a live project? The MEP Pipe Design & Sizing Handbook covers chilled water, refrigerant, fire protection and plumbing/drainage piping with governing formulas, code references and worked examples.



Comments